D9412GV2/D7412GV2 |
Program Entry Guide | 5.0
RADXSKED
EN
| 102
Bosch Security Systems | 5/05 | F001U003636B
Table 33: Programming for Two Same Day Opening Windows (refer to
Figure 5
)
Open Close
W# Day
of
Week
Early
Begin
Start
Stop
Early
Begin
Start
Stop
eXcept On
Holiday
Holiday
Index Area(s)
1
S
M
T W T F S
06: 00
07 : 00
08: 00
Yes /
No
1 2 3 4
1
2 3 4 5 6 7 8
2
S
M
T W T F S
13 : 00
14 : 00
15 : 00
Yes /
No
1 2 3 4
1
2 3 4 5 6 7 8
Do not program a single window to cross the midnight boundary. The window stop time must be later than the
window start time. To program a window that effectively crosses the midnight boundary, you must program two
windows.
For example, to program windows for an area that opens between 11:30 PM and 12:30 AM, five days a week, use
two windows as shown in
Table 34
.
Table 34: Programming to Link Two Days over Midnight
*
Open Close
W# Day
of
Week
Early
Begin
Start
Stop
Early
Begin
Start
Stop
eXcept On
Holiday
Holiday
Index Area(s)
1
S
M T
W
T
F S
22 : 00
23 : 30
23 : 59
Yes
No
1 2 3 4
1
2 3 4 5 6 7 8
2
S
M T
W
T
F
S
00 : 00
00 : 00
00 : 30
Yes
No
1 2 3 4
1
2 3 4 5 6 7 8
* The setting for midnight is 00:00.
W# Close Early Begin
Default:
00: 00
Selection:
HH:MM (hours and minutes)
00:00 to 23:59
Close Early Begin:
This program item is one of three
required to create a Closing Window. To finish
programming a Closing Window, Close Window Start
and Close Window Stop must be programmed.
The time programmed in the Close Early Begin field is
the earliest time the user can close an area before the
Closing Window Start time. If Opening and Closing
Reports are enabled, arming the area between
midnight and the Close Early Begin time generates a
Closing Report. Additionally:
•
If
A# Disable O/C in Window
is set to
Yes
and
the area is armed between the Close Early Begin
time and the Close Window Start time, the
Closing Event is sent with an Early to Close
modifier. If the Close Early Begin time is the same
as the Close Window Start time, no Closing Event
is sent.
•
If
A# Disable O/C in Window
is set to
No
and
the area is armed at any time, a Closing Event is
sent without the Early to Close or late to Close
modifiers.
Arming the area between the Close Window Start and
Close Window Stop times creates a local event in the
control panel event log, but does not send the Closing
Report to the central station.
Arming the area after the Close Window Stop time
and before the next window’s Close Early Begin time
(or midnight, whichever is earlier) generates a Closing
Event with a Late to Close modifier.
When configuring multiple windows to operate on the
same day, ensure that they are added to the system in
chronological order. For example, if three windows are
programmed to execute on Tuesday, Window 1 (W1)
must occur before Window 2 (W2), and Window 2
must occur before Window 3 (W3).
Avoid programming the Open Early Begin
time before a time that is between another
window’s Open Window Start and Open
Window Stop times.
Disabled windows have a blank beginning time. If the
entry for this prompt is blank, but times are
programmed for Close Window Start and Close
Window Stop, the window is disabled.
To disable the window, both the hours and minutes
spaces must be blank.
Содержание D7412GV2
Страница 1: ...EN Program Entry Guide Control Panels D9412GV2 D7412GV2 ...
Страница 76: ...D9412GV2 D7412GV2 Program Entry Guide 2 0 GV2MAIN EN 76 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 98: ...D9412GV2 D7412GV2 Program Entry Guide 4 0 RADXPNTS EN 98 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 134: ...D9412GV2 D7412GV2 Program Entry Guide 6 0 GV2AUX EN 134 Bosch Security Systems 5 05 F001U003636B Notes ...