Installation, assembly and commissioning
for the first time
Version 1.1
Page 75 of 113
4.9
Configuration of the ESS battery
4.9.1
System structure
-
In a complete system of batteries connected in parallel, configure
one
battery
as a “
master”
.
-
In a complete system of batteries connected in parallel, configure
all
other
batteries
as “
slave
”.
-
You can connect up to 6 batteries with each other in parallel.
4.9.2
Addressing the batteries
-
Configure each battery with an unambiguous and unique address.
Numbers 1 to 12 are available.
Each battery must have a different bus address (device address).
4.10
Definition of the battery mode during commissioning and parameter
configuration
Figure 4-25: representation of the BMZ ESS service tool
4.10.1
Single:
This the delivery status of every BMZ ESS 7.0 battery ex-works.
The mode is used for the status: 1 BMZ ESS 7.0 battery operated at one SMA Sunny Island inverter.
4.10.2
Master:
This is the status of a BMZ ESS 7.0 battery in a group of multiple BMZ ESS 7.0 batteries connected in
parallel.
Important: Only one battery may be configured as a master.
The mode is used for the status: multiple BMZ ESS 7.0 batteries are operated at one or more SMA
Sunny Island inverters.
Содержание ESS 7.0
Страница 1: ...OPERATING MANUAL ESS 7 0 ...
Страница 2: ...Version 1 1 Original operating manual ...
Страница 110: ...Annexe Version 1 1 Page 110 of 113 10 1Declaration of conformity Figure 10 1 EC Declaration of Conformity ...
Страница 111: ...Annexe Version 1 1 Page 111 of 113 10 2Warranty card Figure 10 2 warranty card ...
Страница 112: ...Annexe Version 1 1 Page 112 of 113 10 3Installation check list Figure 10 3 installation check list ...
Страница 113: ...Annexe Version 1 1 Page 113 of 113 Figure 10 4 installation check list part 2 ...