Installation, assembly and commissioning
for the first time
Version 1.1
Page 55 of 113
The 50 mm² connection lines must
NOT
be connected to incorrect poles.
Follow the installation manual of the inverter manufacturer.
2
Connect the power cable of the battery inverter to the poles of the NT isolator.
Use the 2 screws of the M8x20 size as well as washers and tension washers.
Figure 4-5: sample representation of the connection of plus and minus power cables with the SMA Sunny Island
inverter
Ensure that the contact surface of cable shoes rests completely.
Maximum tightening torque: 12 Nm. (Tol/- 5 Nm)
3
Connect the CAN communication cable between the inverter and the battery storage system.
For this purpose, patch the patch cable (RJ45) from the
CAN socket
of the battery storage system to the
CAN socket
of the inverter. (Marked in yellow)
Figure 4-6: representation of external connections of the battery system, CAN
4
Insert the NH fuses in the cover of the NH isolator.