Installation, assembly and commissioning
for the first time
Version 1.1
Page 82 of 113
4.13.4
Setting the slave battery address
Address 0 is the default address.
Each battery connected in parallel must have an unambiguous and unique address (device address).
The master and slave batteries function only with the addresses configured with numbers from 1 to
12.
Figure 4-32: representation of configuration of the parameters of a BMZ ESS battery
Important:
1.
Set the “address” (device address) to “2” and configure the battery parameters by clicking on “set
address”.
2.
In a group of multiple BMZ ESS 7.0 batteries connected in parallel,
only one battery
may have the
address “2”.
3.
Configure a unique and unambiguous address (device address) for all other slave batteries.