should be b13.5vdc and +14.0vdc. If the voltage is within range,
record the voltage on the Commissioning / Annual Record Data Sheet and
go to the next Test step. If the voltage is out of range, use a screwdriver to
adjust the voltage on the power supply adjustment mechanism. If the
voltage will not adjust to within range, replace the power supply.
d)
Battery Supply voltage. Measure the Battery Supply voltage on the Battery
connection terminals. The voltage should be b12vdc and +13.8vdc.
If the voltage is within range, record the voltage on the Commissioning /
Annual Record Data Sheet and go to the next Test step.
If the voltage is below range, open the Battery Circuit Breaker. Measure the
DCP Trickle Charge voltage level on the output side (not the input from the
battery) of the circuit breaker. The voltage should be greater than
>+12.2vdc. If voltage level is less than +12.2vdc then the trickle charger is
faulty in the DCP, and will need to be replaced. If the voltage level is
greater than +12.2vdc, then go to Test Step e.
e)
Battery Fluid Levels. Verify the fluid levels in the 6 battery cells. If the
fluid levels are correct, then record the information on the Commissioning /
Annual Record Data Sheet and go to test Step f. If any of the levels are
incorrect, add water to the cell to the required level. Record the
information on the Commissioning / Annual Record Data Sheet and go to
test Step f.
f)
Close the Battery Circuit Breaker.
IV.
Belfort AWOS DCP UHF Data Radio Accuracy Test:
1)
Notify Regional OCC that system is being taken out of service if it is a
commissioned system.
2)
Lower the Tower. Remove the DCP cover. Record the serial number of the DCP
Ritron Model DTX-454 RF Transceiver on the Commissioning / Annual Record
Data Sheet.
3)
Confirm that the HP8920B has been warming up for the minimum of ½ hour
before use. Select the TX function and then FM Demodulation on the HP8920B
front panel.
4)
Connect the DCP to the PC console and open a DOS window. On the PC start the
appropriate version of ACBSTXCOM program provided on the site notebook PC
as follows: enter the DOS command “ACBSTXCOM comx” into the console
starts the ACBSTXCOM program. (Comx is the number of the communications
port that you use for serial communications.) Enter the “M” command at the “-“
prompt. The “Enter Password” message will be displayed. Enter the “Password”.
Access will be granted to the built in hardware tests. This stops all RF
transmission via the DCP RF transceiver.
Содержание AWOS
Страница 17: ... 14 BELFORT INSTRUMENT Proprietary Information Figure 2a Securing the Tower for Maintenance ...
Страница 49: ... 46 BELFORT INSTRUMENT Proprietary Information Figure 9 Temperature Humidity Sensor Removal ...
Страница 51: ... 48 BELFORT INSTRUMENT Proprietary Information Figure 10 Visibility Sensor Removal ...
Страница 60: ...BELFORT INSTRUMENT Proprietary Information Appendix A Belfort AWOS Maintenance Forms ...
Страница 66: ...BELFORT INSTRUMENT Proprietary Information This page intentionally left blank ...
Страница 71: ...BELFORT INSTRUMENT Proprietary Information Appendix B Belfort AWOS Tri Annual Annual 5 Year Maintenance Plan ...
Страница 74: ...BELFORT INSTRUMENT Proprietary Information Appendix C UHF Transceiver Specifications ...
Страница 76: ...BELFORT INSTRUMENT Proprietary Information Appendix D Standard Unicom Radio ICOM A110 VHF Radio Specifications ...
Страница 88: ...BELFORT INSTRUMENT Proprietary Information Appendix F DCP Site Configuration Procedure ...
Страница 93: ...BELFORT INSTRUMENT Proprietary Information Appendix G Belfort AWOS Atomic Clock Verification Procedure ...