5.7
L
IGHTNING
P
ROTECTION
S
YSTEM
,
B
ATTERY
&
T
OWER
T
RI
-A
NNUAL
M
AINTENANCE
SAFETY PRECAUTIONS
1. Before starting any power installation/Maintenance tasks, ensure that the A/C mains power
circuit breaker is in the open position.
2. Do not perform outdoor Belfort AWOS maintenance tasks during a thunderstorm.
3. Use extreme caution when lowering the tilt-over tower whenever ice or snow has accumulated
on the tower cross arm or the sensors. The extra weight may cause the tower to fall over
rapidly.
PARTS AND TOOLS REQUIRED
1.
Two (2) adjustable wrenches 8" (Crescent or equivalent).
2.
Battery Terminal cleaning brush (Sears P/N 00947697000 or equivalent.)
Figure 5
Typical Battery Terminal Brush
3.
Commercial Multi-meter (Fluke 77 or equivalent).
T
RI
-A
NNUAL
I
NSPECTION
/M
AINTENANCE
1.
While the tower is lowered, visually inspect the lightning rod and grounding cable for loose
or corroded electrical connections and mounting hardware.
2.
Clean and secure as required.
3.
Locate the True North monument and verify that it is clearly marked and easily located.
Replace or repaint as needed.
4.
If a battery backup is installed, check the battery cable terminal connections for corrosion
buildup. If corrosion is evident, disconnect the cables from the battery (disconnect the cable
connected to the negative post of the battery first).
5.
Clean battery posts and cable connectors using a battery terminal brush.
6.
If a serviceable lead acid battery is in use, check fluid levels and top up with distilled water per
battery manufacturer’s instructions.
7.
Check the battery voltage open circuit. An acceptable battery should have an open circuit
voltage of 12.6VDC to 13.25VDC. If battery voltage checks low, replace the battery with a
Group 27 deep discharge lead acid battery. Report the battery change in the Facility
Maintenance log.
8.
Reconnect and tighten the positive first and then the negative battery cable to their
corresponding battery terminals.
9.
Check the battery voltage under load. An acceptable battery should have a loaded voltage of
12.1VDC to 12.4VDC. If battery voltage checks low, replace the battery with a Group 27 deep
discharge lead acid battery. Report the battery change in the Facility Maintenance log.
Содержание AWOS
Страница 17: ... 14 BELFORT INSTRUMENT Proprietary Information Figure 2a Securing the Tower for Maintenance ...
Страница 49: ... 46 BELFORT INSTRUMENT Proprietary Information Figure 9 Temperature Humidity Sensor Removal ...
Страница 51: ... 48 BELFORT INSTRUMENT Proprietary Information Figure 10 Visibility Sensor Removal ...
Страница 60: ...BELFORT INSTRUMENT Proprietary Information Appendix A Belfort AWOS Maintenance Forms ...
Страница 66: ...BELFORT INSTRUMENT Proprietary Information This page intentionally left blank ...
Страница 71: ...BELFORT INSTRUMENT Proprietary Information Appendix B Belfort AWOS Tri Annual Annual 5 Year Maintenance Plan ...
Страница 74: ...BELFORT INSTRUMENT Proprietary Information Appendix C UHF Transceiver Specifications ...
Страница 76: ...BELFORT INSTRUMENT Proprietary Information Appendix D Standard Unicom Radio ICOM A110 VHF Radio Specifications ...
Страница 88: ...BELFORT INSTRUMENT Proprietary Information Appendix F DCP Site Configuration Procedure ...
Страница 93: ...BELFORT INSTRUMENT Proprietary Information Appendix G Belfort AWOS Atomic Clock Verification Procedure ...