Commissioning
EL5101, EL5101-0010, EL5101-0011
136
Version: 4.2
Note
Parameterization
The terminal is parameterized via the
CoE - Online tab [
}
129]
(double-click on the respec-
tive object) or via the
Process Data tab [
}
129]
(allocation of PDOs).
6.4.2.2.1
Restore object
Index 1011 Restore default parameters
Index (hex) Name
Meaning
Data type
Flags
Default
1011:0
Restore default param-
eters
Restore the default settings
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to “
0x64616F6C”
in the set value di-
alog, all backup objects are reset to their delivery state.
Note: Some FW versions also accept the following in-
put:
"0x6C6F6164".
UINT32
RW
0x00000000
(0
dec
)