Commissioning
EL5101, EL5101-0010, EL5101-0011
143
Version: 4.2
6.4.2.2.4
Output data
Index 7000 ENC Outputs (EL5101-0010)
Index (hex) Name
Meaning
Data type
Flags
Default
7000:0
ENC Outputs
Maximum subindex
UINT8
RO
0x11 (17
dec
)
7000:01
Enable latch C [
}
133]
Activate latching via input “C”.
BOOLEAN
RO
0x00 (0
dec
)
7000:02
Enable latch extern on
positive edge [
}
133]
Activate external latch with positive edge.
BOOLEAN
RO
0x00 (0
dec
)
7000:03
Set counter
Set counter
BOOLEAN
RO
0x00 (0
dec
)
7000:04
Enable latch extern on
negative edge [
}
133]
Activate external latch with negative edge.
BOOLEAN
RO
0x00 (0
dec
)
7000:11
Set counter value
The counter value to be set via “Set counter” (index
7000:03 [
}
143]
).
UINT32
RO
0x00000000
(0
dec
)
Index 7010 ENC Outputs (EL5101-0000)
Index (hex) Name
Meaning
Data type
Flags
Default
7010:0
ENC Outputs
Maximum subindex
UINT8
RO
0x11 (17
dec
)
7010:01
Enable latch C [
}
133]
Activate latching via input “C”.
BOOLEAN
RO
0x00 (0
dec
)
7010:02
Enable latch extern on
positive edge [
}
133]
Activate external latch with positive edge.
BOOLEAN
RO
0x00 (0
dec
)
7010:03
Set counter
Set counter
BOOLEAN
RO
0x00 (0
dec
)
7010:04
Enable latch extern on
negative edge [
}
133]
Activate external latch with negative edge.
BOOLEAN
RO
0x00 (0
dec
)
7010:11
Set counter value
The counter value to be set via “Set counter” (index
0x7010:03 [
}
143]
).
UINT32
RO
0x00000000
(0
dec
)
6.4.2.2.5
Information / diagnostic data (channel specific)
Index A000 ENC Diag data (EL5101-0010)
Index (hex) Name
Meaning
Data type
Flags
Default
A000:0
ENC Diag data
Maximum subindex
UINT8
RO
0x04 (4
dec
)
A000:01
Open circuit A [
}
134]
Open circuit on track A
BOOLEAN
RO
0x00 (0
dec
)
A000:02
Open circuit B [
}
134]
Open circuit on track B
BOOLEAN
RO
0x00 (0
dec
)
A000:03
Open circuit C [
}
134]
Open circuit on track C
BOOLEAN
RO
0x00 (0
dec
)
A000:04
Field power failure
Field bus voltage error
BOOLEAN
RO
0x00 (0
dec
)
Index A010 ENC Diag data (EL5101-0000)
Index (hex) Name
Meaning
Data type
Flags
Default
A010:0
ENC Diag data
Maximum subindex
UINT8
RO
0x03 (3
dec
)
A010:01
Open circuit A [
}
134]
Open circuit on track A
BOOLEAN
RO
0x00 (0
dec
)
A010:02
Open circuit B [
}
134]
Open circuit on track B
BOOLEAN
RO
0x00 (0
dec
)
A010:03
Open circuit C [
}
134]
Open circuit on track C
BOOLEAN
RO
0x00 (0
dec
)
6.4.2.2.6
Standard objects
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
Index (hex) Name
Meaning
Data type
Flags
Default
1000:0
Device type
Device type of the EtherCAT slave: the Lo-Word con-
tains the CoE profile used (5001). The Hi-Word con-
tains the module profile according to the modular de-
vice profile.
UINT32
RO
0x00001389
(5001