Mounting and wiring
EL5101, EL5101-0010, EL5101-0011
47
Version: 4.2
Connection
Terminal point
No.
Comment
A
1
Encoder input A
B
2
Encoder input B
C
3
Encoder input C
Latch 24 V
4
Latch input
¬A
5
Encoder input A
¬B
6
Encoder input B
¬C
7
Encoder input C
Gate 24 V
8
Gate input
Ue = +5 V
1
'
+5 V encoder supply
+24 V
2
'
+24 V (internally connected to terminal point 6
'
and positive power contact)
0 V
3
'
0 V (internally connected to terminal point 7
'
and negative power contact)
Input 1
4
'
Status input 1
Alarm input from rotary encoder. Internally connected to 5 V via pull-up.
Switching to negative potential, i.e. connection to GND leads to error bit and
LED display. If externally supplied (not recommended) 5 V max. against GND is
permitted.
Uo = 0 V
5
'
0 V encoder supply
+24 V
6
'
+24 V (internally connected to terminal point 2
'
and positive power contact)
0 V
7
'
0 V (internally connected to terminal point 3
'
and negative power contact)
Shield
8
'
Screen
LEDs
LED
Color
Meaning
INPUT A, B, C green
indicates TRUE level
INPUT 1
red
is lit, if INPUT 1 is connected to GND
[INPUT 1 is connected to an internal 5 V HIGH level though internal pull-up
(default)]
LATCH
green
is lit, if a signal (+24 V) is connected to the latch input
GATE
green
is lit, if a signal (+24 V) is connected to the gate input
RUN
green
This LED indicates the terminal's operating state:
off
State of the
EtherCAT State Machine [
}
23]
:
INIT
= initialization of the
terminal or
BOOTSTRAP
= function for
firmware updates [
}
177]
of the
terminal
flashing
State of the EtherCAT State Machine:
PREOP
= function for mailbox
communication and different standard-settings set
single
flash
State of the EtherCAT State Machine:
SAFEOP
= verification of the
Sync Manager [
}
98]
channels and the distributed clocks.
Outputs remain in safe state
on
State of the EtherCAT State Machine:
OP
= normal operating state;
mailbox and process data communication is possible
POWER 5 V
green
Operating voltage display for incremental encoder power supply