Commissioning
EL5101, EL5101-0010, EL5101-0011
138
Version: 4.2
Index 8000 ENC Settings (EL5101-0010)
Index (hex) Name
Meaning
Data type
Flags
Default
8000:15
Frequency resolution
[
}
132]
Resolution of the frequency measurement:
100: “0.01 Hz”
UINT16
RW
0x0064
(100
dec
)
8000:16
Period resolution
[
}
132]
Internal resolution of the period measurement:
100: “100 ns” period value is a multiple of 100 ns
The period is calculated internally with a resolution of
100 ns. The max. measurable period can then be ap-
prox. 1.6 seconds.
500: “500 ns” period value is a multiple of 500 ns
Internally the period is calculated with 500 ns resolu-
tion. The maximum measurable period is approx.
32.7 ms. The resolution of process data continues to
be the value according to index
0x8000:14 [
}
137]
(e.g.
100 ns [default]).
UINT16
RW
0x0064
(100
dec
)
8000:17
Frequency Wait Time
[
}
132]
Waiting time [ms] for frequency measurement
Once the time specified in the
frequency window
[
}
132]
has elapsed, the system waits for the next posi-
tive edge from track A. This enables the update speed
for the Frequency process data to be optimized, de-
pending on the expected frequencies. At least double
the period of the minimum frequency to be measured
should be entered here. t >= 2* (1 / f
min
)
UINT16
RW
0x0190
(400
dec
)