Mounting and wiring
EL31xx-00xx
78
Version: 5.9
LEDs
LED
Color
Meaning
RUN*
green
This LED indicates the terminal's operating state (if more than one RUN LED is present, all of them have the
same function):
off
State of the
EtherCAT State Machine [
}
36]
:
INIT
= initialization of the terminal or
BOOT-
STRAP
= function for
firmware updates [
}
211]
of the terminal
flashing
State of the EtherCAT State Machine:
PREOP
= function for mailbox communication and dif-
ferent standard-settings set
single flash
State of the EtherCAT State Machine:
SAFEOP
= verification of the
Sync Manager [
}
143]
channels and the distributed clocks.
Outputs remain in safe state
on
State of the EtherCAT State Machine:
OP
= normal operating state; mailbox and process data
communication is possible
ERROR**
red
Fault indication in the event of broken wire or undershooting or overshooting of the measuring range
*) If several RUN LEDs are present, all of them have the same function
**) The error display shows the signal processing state for each channel
Connection EL3174, EL3174-0090
Terminal point
Description
Designation
No.
Ch1 U+
1
+ Input 1 voltage measurement (U+)
Ch2 U+
2
+ Input 2 voltage measurement (U+)
Ch3 U+
3
+ Input 3 voltage measurement (U+)
Ch4 U+
4
+ Input 4 voltage measurement (U+)
+24 V
5
+24 V (internally connected to positive power contact)
+24 V
6
+24 V
7
+24 V
8
Ch1 U-
9
- Input 1 voltage measurement (U-)
Ch2 U-
10
- Input 2 voltage measurement (U-)
Ch3 U-
11
- Input 3 voltage measurement (U-)
Ch4 U-
12
- Input 4 voltage measurement (U-)
Input Ch1
13
Input 1 current measurement (I)
Input Ch2
14
Input 2 current measurement (I)
Input Ch3
15
Input 3 current measurement (I)
Input Ch4
16
Input 4 current measurement (I)
Connection EL3174-0002, EL3174-0032
Terminal point
Description
Designation
No.
+ Input 1
1
+ Input 1 voltage-/ current measurement (U/ I)
+ Input 2
2
+ Input 2 voltage-/ current measurement (U/ I)
+ Input 3
3
+ Input 3 voltage-/ current measurement (U/ I)
+ Input 4
4
+ Input 4 voltage-/ current measurement (U/ I)
- Input 1
5
- Input 1 voltage-/ current measurement (U/ I)
- Input 2
6
- Input 2 voltage-/ current measurement (U/ I)
- Input 3
7
- Input 3 voltage-/ current measurement (U/ I)
- Input 4
8
- Input 4 voltage-/ current measurement (U/ I)
4.12
Connection notes for 20 mA measurement
4.12.1
Configuration of 0/4..20 mA differential inputs
This section describes the 0/4..20 mA differential inputs for terminal series EL301x, EL302x, EL311x,
EL312x and terminals EL3174, EL3612, EL3742 and EL3751.
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...