Commissioning
EL31xx-00xx
165
Version: 5.9
Terminal
Swap limit function from
EL31x1, EL31x4
All firmware versions
EL3112-0011
All firmware versions
EL3102
Firmware 08
EL3112
Firmware 08
EL3122
Firmware 08
EL3142
Firmware 08
EL3152
Firmware 09
EL3162
Firmware 08
EL3174, EL3174-00xx
All firmware versions
5.6.2.5
Operating modes
The EL30xx and the EL31xx accordingly supports three different operating modes: Freerun (filter on, timer
interrupt), Synchron (filter off, SyncManager interrupt) and DC (DC Sync interrupt)
Fig. 181: Relationship of operating modes
The terminal switches between the Freerun (filter on) and Synchron modes by activating/deactivating the
filter via the index. The terminal remains in OP mode during this process. The changeover may result in
longer sampling times and step changes in the process data until the filters have assumed a steady state.
DC mode can only be used when the filters are switched off. Likewise, it is not possible to switch the filters
on in DC mode. The DC mode is parameterized via the DC tab in the TwinCAT System Manager.
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...