Product overview
EL31xx-00xx
30
Version: 5.9
2.7.2
EL3174, EL3174-0090 - Technical data
Technical data
EL3174
EL3174-0090
Analog inputs
4 (U differential, I single-ended)
Conversion type
simultaneous
ADC type
SAR
Signal voltage
-10/0…+10 V
Signal current
-20/0/+4…+20 mA
Measuring range, nominal (Full
Scale Value)
Voltage measurement range
-10/0…+10 V
Current measurement range
-20/0/+4…+20 mA
Measuring range, technical
Voltage measurement range
-10.73…+10.73 V
Current measurement range
-21.47…+21.47 mA
Measuring error
(full measuring range)
< ±0.3 % (relative to full scale value)
Distributed Clocks
yes
Distributed Clocks precision
<< 1 µs
Resolution
16 bit (incl. sign)
Internal resistance
Voltage measurement: > 200 kΩ | Current measurement: 85 Ω typ.
Input filter limit frequency
5 kHz
Common-mode voltage U
CM
35 V max. (voltage measurement)
Minimal EtherCAT cycle time
200 µs
500 µs
Overcurrent protection
50 mA typ.
Bit width of the process image
Inputs: 16 Byte
Inputs: 35 Byte
Outputs: 6 Byte
Configuration
no address or configuration settings required
MTBF (+55°C)
-
>800.000 h
Special features
U/I parameterisable, Extended Range, standard and compact
process image, activatable FIR/IIR filters
EL3174-0090 with TwinSAFE SC technology
Supply voltage for electronic
via the E-bus
Current consumption via E-bus
typ. 170 mA
Electrical isolation
500 V (E bus/ fieldbus voltage)
Recommended operating voltage
range (ground related to GND/ 0V
power contact)
Voltage measurement range
U
CM
35 V max.
Current measurement range
single ended,
dielectric strength max. 30 V
Recommended signal range
Voltage measurement range
Extended Range (107%), differential
Current measurement range
Extended Range (107%), single ended
Destruction limit
(ground related to GND/ 0V
power contact)
Voltage measurement range
50 V
Current measurement range
30 V
Destruction limit
(differential)
Voltage measurement range
50 V
Current measurement range
n.a.
Weight
approx. 65 g
Permissible ambient temperature range during operation
0…+55 °C
Permissible ambient temperature range during storage
-25…+85 °C
Permissible relative humidity
95 %, no condensation
Design
HD (High Density) housing with signal LED
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [
}
43]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
cULus [
}
56]
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...