Product overview
EL31xx-00xx
23
Version: 5.9
2.4.2
EL314x - Technical data
Technical data
EL3141-0000
EL3142-0000
EL3142-0010
EL3144-0000
analog inputs
1 (single ended) 2 (single ended)
4 (single ended)
Signal current
0 mA…20 mA
0 mA…20 mA
-10 mA…+10 mA
0 mA…20 mA
Distributed Clocks
yes
yes (from
rev.
EL314x-0000-0017
[
}
206]
)
yes (from
rev.
EL314x-0010-0017 [
}
206]
)
yes
Distributed Clocks preci-
sion
<< 1 µs
Internal resistance
85 Ω type. + diode voltage
Input filter limit frequency
5 kHz
Dielectric strength
max. 30 V
Conversion time (default
setting: 50 Hz filter)
approx. 40 µs
approx. 60 µs
(Fast mode: approx. 40 µs)
approx. 100 µs
Resolution
16 bit (including sign)
Measuring error (full mea-
suring range)
< ± 0.3% (at 0 °C ... +55 °C, relative to
the full scale value)
< ± 0.5% (when the extended tempera-
ture range is used)
< ± 0.3% (at 0 °C ... +55
°C, relative to the full scale
value)
< ± 0.3% (at 0 °C ... +55
°C, relative to the full scale
value)
< ± 0.5% (when the ex-
tended temperature range
is used)
Supply voltage for elec-
tronic
via the E-bus
Current consumption via
E-bus
typ. 130 mA
typ. 170 mA
typ. 170 mA
typ. 130 mA
Electrical isolation
500 V (E-bus/field voltage)
Bit width of the process im-
age (default setting)
Inputs: 1 x
16 bit;
Status: 1 x 8 bit
Inputs: 2 x 16 bit;
Status: 2 x 8 bit
Inputs: 4 x 16 bit;
Status: 4 x 8 bit
Configuration
no address or configuration settings required
Weight
approx. 55 g
Permissible ambient tem-
perature range during op-
eration
-25°C ... +60°C (extended temperature range)
Permissible ambient tem-
perature range during stor-
age
-40°C ... +85°C
Permissible relative humid-
ity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [
}
43]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27,
see also
Installation instructions for enhanced mechanical load capacitiy [
}
47]
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
55]
cULus [
}
56]
CE
cULus [
}
56]
CE
ATEX [
}
55]
cULus [
}
56]
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...