Commissioning
EL31xx-00xx
171
Version: 5.9
Legend
Bit
Name
Description
SW.15
TxPDO Toggle
1
bin
Toggles with each new analog process value
SW.14
TxPDO State
1
bin
TRUE in the case of an internal error
SW.13* Sync error
1
bin
TRUE (DC mode): a synchronization error occurred in the expired cycle.
SW.6
ERROR
1
bin
General error bit, is set together with overrange and underrange
SW.5
Limit 2
1
bin
See
Limit [
}
163]
SW.4
1
bin
SW.3
Limit 1
1
bin
See
Limit [
}
163]
SW.2
1
bin
SW.1
Overrange
1
bin
Analog input signal lies above the upper permissible threshold for this terminal
SW.0
Underrange
1
bin
Analog input signal lies under the lower permissible threshold for this terminal
*) from rev. EL31xx-0000-0016
Control word
The EL31xx have no control word
Changeover of process data sets
The process data to be transmitted (PDO, ProcessDataObjects) can be selected by the user
• completely for all channels via the selection dialog “Predefined PDO Assignment” (all TwinCAT
versions)
• selective for individual PDOs, taking into account the excluded elements.
“Predefined PDO Assignment” selection dialog (from TwinCAT 2.11 build 1544 onwards)
Defined PDO sets can be preselected if they exist in the XML description.
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...