Commissioning
EL31xx-00xx
163
Version: 5.9
5.6.2.2
Siemens bits, index 0x80n0:05
Siemens bits, index
0x80n0:05 [
}
194]
If this bit is set, status displays are superimposed on the lowest three bits. In the error case "overrange" or
"underrange", bit 0 is set.
5.6.2.3
Undershoot and overshoot of the measuring range (under-range, over-
range), index 0x60n0:01, 0x60n0:02
Undershoot and overshoot of the measuring range (under-range, over-range), index
0x60n0:01
[
}
196]
,
0x60n0:02 [
}
196]
Chapter
Data stream and correction calculation [
}
178]
contains a clear description of the correction
calculation between the raw values and the output values if the limit ranges are exceeded.
5.6.2.4
Limit 1 and limit 2, Swap Limit Bits
Limit 1 and limit 2, index
0x80n0:13, [
}
194]
index
0x80n0:14 [
}
194]
If the value exceeds or falls below these values, which can be entered in the indices
0x80n0:13 [
}
194]
and
0x80n0:14 [
}
194]
, then the bits in the indices
0x60n0:03 [
}
196]
and
0x60n0:05 [
}
196]
are set accordingly
(see example below). The indices
0x80n0:07 [
}
194]
or
0x80n0:08 [
}
194]
serve to activate the limit value
monitoring.
Output limit n (2-bit):
• 0: not active
• 1: Value is smaller than the limit value
• 2: Value is larger than the limit value
• 3: Value is equal to the limit value
Limit evaluation
The limit evaluation assumes a signed representation. The conversion to the desired representation
(index
0x80n0:02 [
}
194]
) only takes place after the limit evaluation.
Note on linking in the PLC with 2-bit values
Linking in the PLC with 2-bit values
The limit information consists of 2 bits. Limitn can be linked to the PLC or a task in the System Man-
ager.
• PLC:
IEC61131-PLC contains no 2-bit data type that can be linked with this process data directly. For
transferring the limit information, define an input byte (e.g. see Fig.
Input byte
definition) and link the
limit to the
VariableSizeMismatch
dialog, as described in section Note about the 1-byte status of earlier
EtherCAT Terminals.
Fig. 179: Input byte definition
• Additional task
2-bit variables can be created in the System Manager.
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...