Mounting and wiring
EL31xx-00xx
54
Version: 5.9
4.7
ATEX - Special conditions (standard temperature
range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
standard temperature range in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of
at least IP54 in accordance with EN 60529! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus com-
ponents standard temperature range in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or
if a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with standard temperature range certified for potentially explosive areas
bear one of the following markings:
II 3G KEMA 10ATEX0075 X Ex nA IIC T4 Gc Ta: 0 … 55°C
or
II 3G KEMA 10ATEX0075 X Ex nC IIC T4 Gc Ta: 0 … 55°C
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...