Object overview
• Restore object
• Configuration data
• Input data [
}
196]
• Output data [
}
197]
• Standard objects [
}
197]
Note regarding EL31x2 terminals before rev. no. EL31x2-0000-0016
The following CoE object list additionally contains the objects for the 2-channel input terminals be-
fore rev. no. EL31x2-0000-0016. These objects are mirrored to the standardized objects of MDP
profiles 300 (analog inputs). When a new configuration is created in TwinCAT, we recommend us-
ing the standardized objects based on channel profile 300, although linking with the objects high-
lighted in color should be avoided. Older configurations are compatible in the event of replacement,
see also section
"Process data" [
}
161]
.
Note regarding firmware versions for EL31x2 terminals
For compatibility reasons, in addition to regular settings objects in CoE range 0x8000, the EL31x2
also support the predecessor objects in the range 0x4000. The settings objects in the range 0x4000
no longer show up in the CoE overview from the following FW versions, although they are still func-
tionally supported:
EL3101-0000 FW12
EL3112-0000 FW13
EL3122-0000 FW13
EL3142-0000 FW13
EL3142-0010 FW11
EL3152-0000 FW14
EL3162-0000 FW13
5.8.1
Restore object
Index 1011 Restore default parameters
Index (hex) Name
Meaning
Data type
Flags
Default
1011:0
Restore default
parameters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to “
0x64616F6C”
in the set value dialog,
all backup objects are reset to their delivery state.
UINT32
RW
0x00000000
(0
dec
)
5.8.2
Configuration data
Index 40n0* producer code word (for n = 4 [channel 1], n = 8 [channel 2])
Producer code word
The vendor reserves the authority for the basic calibration of the terminals. The Producer code word
is therefore at present reserved.
*) up to rev. no. EL31x2-0000-0016, only for EL31x2, see
note regarding EL31x2 terminals before rev. no.
EL31x2-0000-0016 [
}
191]
Index 40n1 ADC raw value (for n = 4 [channel 1], n = 8 [channel 2])
(up to rev. no. EL31x2-0000-0016, only for EL31x2, see
note [
}
191]
)
Index (hex) Name
Meaning
Flags
Default
40n1:0
ADC raw value
Length of this object
RO
1
dec
40n1:01
ADC rawdata
This is the circuit's raw ADC value. It is converted to a measurement
through a calculation with the gain and offset from the calibration.
RO
-
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...