Commissioning
EL31xx-00xx
168
Version: 5.9
Fig. 182: Attenuation curve notch.filter at 50 Hz
Filter data for FIR filter (1 to 4-channel terminals)
Filter
Attenuation
Limit frequency (-3 dB)
Conversion time
50 Hz FIR
> 50 dB
22 Hz
625 µs
60 Hz FIR
> 45 dB
26 Hz
521 µs
IIR filter
The filter with IIR characteristics is a discrete time, linear, time invariant filter that can be set to eight levels
(level 1 = weak recursive filter, up to level 8 = strong recursive filter).
The IIR can be understood to be a moving average value calculation after a low-pass filter.
Through the synchronization mode
FreeRun
the IIR filter operates with an internal cycle time of 180 µs (1 or
2 channels) or 500 µs (4 channels).
IIR filter
EL31x1, EL31x2, sampling time 180 µs
EL31x4, sampling time 500 µs
Limit frequency (-3 dB)
Limit frequency (-3 dB)
IIR 1
1 kHz
400 Hz
IIR 2
500 Hz
220 Hz
IIR 3
285 Hz
100 Hz
IIR 4
142 Hz
50 Hz
IIR 5
66 Hz
24 Hz
IIR 6
33 Hz
12 Hz
IIR 7
17 Hz
6.2 Hz
IIR 8
8.2 Hz
3.0 Hz
Содержание EL3101
Страница 1: ...Documentation EL31xx 00xx Analog Input Terminals 16 Bit 5 9 2018 08 28 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL31xx 00xx 6 Version 5 9...
Страница 52: ...Mounting and wiring EL31xx 00xx 52 Version 5 9 Fig 33 Other installation positions...
Страница 123: ...Commissioning EL31xx 00xx 123 Version 5 9 Fig 118 Incorrect driver settings for the Ethernet port...
Страница 134: ...Commissioning EL31xx 00xx 134 Version 5 9 Fig 137 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...