Limit operating temperatures
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Water in cooling mode
+7 °C / +25 °C
+7 °C / +25 °C
+7 °C / +25 °C
Outdoor air in cooling mode
+10 °C/+46 °C
+7 °C/+46 °C
+7 °C/+46 °C
Tab.4
Heating mode: outside air tempe7 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
4.60
5.82
7.65
Coefficient of Performance (COP)
5.11
4.22
4.55
Absorbed electrical power
kWe
0.90
1.38
1.68
Nominal water flow rate (ΔT = 5 K)
m
3
/h
0.80
1.00
1.32
Tab.5
Heating mode: outdoor air tempe2 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
3.47
3.74
6.75
Coefficient of Performance (COP)
3.97
3.37
3.43
Absorbed electrical power
kWe
0.88
1.11
1.97
Tab.6
Cooling mode: outdoor air tempe35 °C, water temperature at the 18 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Cooling output
kW
4.12
5.08
7.91
Energy efficiency ratio (EER)
4.32
4.20
4.27
Absorbed electrical power
kWe
0.95
1.21
1.85
Tab.7
Common specifications
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Total dynamic head at nominal flow rate
kPa
65
55
30
Nominal air flow rate
m
3
/h
2680
2700
3300
Power voltage of the outdoor unit
V
230
230
230
Start-up amperage
A
5
5
5
Maximal amperage
A
12
13
17
Acoustic power - Inside
dB(A)
30
39
39
Acoustic power - Outside
dB(A)
55
62
66
R410A refrigerant fluid load
kg
1.3
1.4
3.2
R410A refrigerant fluid load
tCO
2
e
2.714
2.923
6.680
Refrigerant connection (Liquid - Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
Max. pre-charged length
m
7
10
10
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 55 °C
(inside and outside)
(2) The quantity of refrigerant fluid in tonnes of CO
2
equivalent is calculated using the following formula: quantity (in kg) of refrigerant fluid x
GWP/1000. The Global Warming Potential (GWP) of R410A gas is 2088.
3.2.2
Heat pump weight
Tab.8
Indoor module
Data
Unit
MIC V200
Weight empty
kg
177
Total weight with water
kg
393
3 Technical specifications
14
7654506 - v06 - 19112019
Содержание MIC V200
Страница 138: ...14 Appendix 138 7654506 v06 19112019 ...
Страница 140: ...7654506 v06 19112019 7654506 001 06 ...