5. Access the languages available by pressing the
key.
6. Select the language by pressing the or keys until the desired
language is displayed.
7. Confirm by pressing the
key.
8. Go back to the main display by pressing the
h
key.
7.3.2
Selecting the type of outdoor unit and the type of back-up
(CN1 et CN2)
The configuration numbers must be reset if the EHC–06 PCB is replaced
or if there is a setting error. To reset the configuration numbers:
1. Go to the Installer menu.
2. Access the Installer menu: enter the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Access the EHC–06 PCB parameters by pressing the or key.
5. Select the CNF menu (control panel reset) by pressing the or
keys.
6. Confirm by pressing the
key.
7. Enter the values corresponding to the type of outdoor unit and the
type of back-up by pressing on the or key.
Important
The CN1 and CN2 values are indicated on the appliance's data
plate.
8. Confirm the selection by pressing the
key.
9. Go back to the main display by pressing the
h
key.
CNF Menu
The CNF menu is used to configure the heat pump according to the type
of back-up and the output of the outdoor unit installed.
Tab.47 Value of the CN1 and CN2 parameters with an electrical back-
up
Output of the outdoor unit
CN1
CN2
4.5 kW
17
3
6 kW
7
3
8 kW
8
3
Fig.91
MW
-5
0
0
0
4
0
5
-2
Fig.92
MW
-5
0
0
0
4
0
7
-2
Fig.93
MW
-5
0
0
0
0
2
6
-5
Fig.94
MW
-6
0
0
0
3
6
7
-3
7 Settings
7654506 - v06 - 19112019
73