9.4.3
Shutting down the cooling function
Important
If the heating function is shut off, then the cooling will also be shut
off.
1. Access the menu.
2. Confirm access by pressing the
key.
3. Select CIRCA or CIRCB by pressing the or key.
4. Confirm the selection by pressing the
key.
5. Select TP.C by pressing the or keys.
6. Confirm the selection by pressing the
key.
7. Modify the timer program to stop cooling.
9.5
Frost Protection
If the temperature of the heating water in the heat pump falls too much,
the integrated protection device switches itself on. This device functions as
follows:
If the water temperature is lower than 5°C, the circulating pump starts
up.
If the water temperature is lower than 3°C, the back-up starts up.
If the water temperature is higher than 10°C, the back-up shuts down
and the circulating pump continues to run for a short time.
The radiator valves in rooms where there is a risk of frost must be fully
open.