Status Appliance: AM012 parameter
Appliance sub status: AM014 parameter
8= controlled compressor shut-down
Controlled Stop
00= off: the heating or cooling set point has been reached
01= anti-short cycle
The heating set point has been reached. The compressor is not authorised to
restart.
60= pump post-operation
Heat pump and back-up shut-down, system pump post-operation.
67= the outside temperature is lower than the compressor's maximum operat
ing temperature
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
75= compressor shut-down owing to the condensation detector
76= compressor shut-down owing to the flow rate
79= compressor and back-up bypass in heating / domestic hot water mode
80= compressor and back-up bypass in cooling mode
82= temperature lower than the minimum cooling temperature
Compressor shut-down.
9
Blocking Mode
30= normal operation.
The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down, system pump running.
65= compressor bypass
The back-ups are operating.
66= the temperature exceeds the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operat
ing temperature
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not met
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
88 = BL-Back-up limited
Back-ups shed
89 = BL-Heat pump limited
Compressor shed
90 = BL-Heat pump & back-up limited
Compressor and back-ups shed
91 = BL-Off-peak rate
Off-peak cost
92 = PV-with Heat pump
Photovoltaic powered by compressor only
93 = PV-with Heat pump & back-up
Photovoltaic powered by compressor and back-ups
94 = BL-Smart Grid
Smart Grid Ready function
10
Locking Mode
11
Load test min
7 Settings
7654506 - v06 - 19112019
89