Tab.56 Operation of the heat pump in a Smart Grid
BL1 IN input
BL2 IN input
Operating
Inactive
Inactive
Normal: The heat pump and the electrical back-up operate normally
Active
Inactive
Shutdown: The heat pump and the electrical back-up are shut down
Inactive
Active
Economy: The heat pump voluntarily overheats the system without the electrical
back-up
Active
Active
Super Economy: The heat pump voluntarily overheats the system with the electrical
back-up
Overheating is activated depending on whether the dry contact on inputs
BL1 and BL2 is open or closed, and the AP098 and AP099 parameters
which control the activation of functions depending on whether the
contacts are open or closed.
1. Connect the Smart Grid signal inputs to the BL1 IN and BL2 IN inputs
on the EHC–06PCB. Smart Grid signals come from dry contacts.
Germany: Connect the SG1 and SG2 terminals respectively from the
electricity meter to the BL1 IN and BL2 IN inputs on the EHC–06
power circuit board.
2. Set the AP001 and AP100 parameters to 10.
The heat pump is ready to receive and manage Smart Grid signals.
3. Choose the contact directions of the BL1 IN and BL2 IN multifunction
inputs by setting the AP098 and AP099 parameters.
Tab.57
Parameter
Description
AP098
Configuration of the BL1 contact direction
0 = input active on open contact
1 = input active on close contact
AP099
Configuration of the BL2 contact direction
0 = input active on open contact
1 = input active on close contact
4. Configure the temperature offsets for the voluntary overheating by
configuring the HP091 and HP092 parameters.
Tab.58
Parameter
Description
HP091
Heating set point temperature offset when the Photovoltaic function is running
HP092
Domestic hot water set point temperature offset when the Photovoltaic function is running
7.3.12 Reducing the noise level of the outdoor unit
Silent mode is used to reduce the noise level on the outdoor unit during a
given time range, particularly at night. This mode gives temporary
precedence to silent running rather than temperature control.
Important
Silent mode only operates if the silent running kit is connected
to the outdoor unit.
This function is not compatible with the AWHP 4.5 MRoutdoor
unit.
Silent mode is managed by the following parameters which can be found
in the Installer menu, EHC–06, ADV:
7 Settings
7654506 - v06 - 19112019
79