ADV
Description of the ADV advanced parameters
Factory setting
EHC–06
Factory setting
SCB-04
AP072
Humidity sensor configuration
0 =No
1 =OnOff
2 =0-10V sensor
0
AP101
De-air cycle settings
0 =No deair at power up
1 =Always deair at pwr
2 =Deair only at 1 pwr
1
not available
AP102
Configuration of the boiler pump as zone pump or system pump
(feed lowloss header)
0 =No
1 =Yes
1
not available
HP : Heat-pump Parameters = Heat pump parameters
Tab.45
ADV parameter
Description of the ADV advanced parameters
Factory setting
EHC–06
HP003
Minimum flow temperature of the heat pump in cooling mode
Can be set from 5 °C to 30 °C
5
HP010
Minimum flow rate
Can be set from 0 l/min to 90 l/min
5 for 4.5 kW
5 for 6 kW
8 for 8 kW
HP011
Flow rate that triggers a warning message indicating that flow rate becomes
insufficient
Can be set from 0 l/min to 95 l/min
7 for 4.5 kW
7 for 6 kW
9 for 8 kW
HP030
Delay time for starting the backup energy source for the heating circuits
Can be set from 0 Min to 600 Min
20
HP031
Delay time for stopping the backup energy source for the heating circuits
Can be set from 0 Min to 600 Min
0 = auto mode: use parameters HP047 to HP050
4
HP033
Value of the pulse coming from the electrical counter
Can be set from 0 Wh to 1000 Wh
1
HP047
Delay for starting the backup when the outdoor temp. is equal to the parameter
Max.Outdoor T. backup
Can be set from 1 to 10 minutes
Value accepted when HP031 = 0
8
HP048
Delay for starting the backup when the outdoor temp. is equal to the parameter
Max.Outdoor T. backup
Can be set from 0 to 60 minutes
Value accepted when HP031 = 0
30
HP049
Minimum outdoor temperature related to the parameter Delay Min.Outdoor T.
Can be set from -30 to 0 °C
Value accepted when HP031 = 0
-10
HP050
Maximum outdoor temperature related to the parameter Delay Max.Outdoor T.
Can be set from -30 to +20 °C
Value accepted when HP031 = 0
15
HP051
Minimum operating temperature for the heat pump
Can be set from -20 to +5 °C
-15 °C for 4.5 kW
-15 °C for 6 kW
-20 °C for 8 kW
HP058
Enabling heat pump silent mode
0 =No
1 =Yes
Requires a specific option. Not available for AWHP 4.5 MR.
0
7 Settings
7654506 - v06 - 19112019
71