6. Configure the HP033 parameters according to the type of energy
meter installed. By default, the pulse weight is set to 1 Wh, the setting
range of the HP033 parameter goes from 0 (no metering) to 1000 Wh.
If the pulse weight is in kWh, use the following table.
Tab.49 If the pulse weight is given in kWh
Any numbers other than those stated in the table will not work.
Number of pulses per kWh
Value to be configured for
the HP033 parameter
1000
1
500
2
250
4
200
5
125
8
100
10
50
20
40
25
25
40
20
50
10
100
8
125
5
200
4
250
2
500
1
1000
7. Configure the HP034 and HP035 parameters.
Tab.50
Situation
Configuration
If an electrical back-up
is fitted
Set the HP034 and HP035 parameters according to the configuration of the electrical back-up stages
output.
7.3.5
Configuring a convection fan or underfloor cooling
This function is only available when the type of circuit selected is
underfloor heating or a convection fan: CP020 parameter set to 2 or 5.
Important
The heating should be activated in order for cooling to function.
1. Go to the Installer menu.
2. Access the Installer menu by entering the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Access the EHC–06 PCB parameters by pressing the or key.
5. Select the AP028 parameter corresponding to cooling by pressing the
or keys.
6. Confirm by pressing the
key.
7. Select value 1 by pressing the key to activate the cooling function.
Fig.96
MW
-4
0
0
0
1
9
7
-2
7 Settings
7654506 - v06 - 19112019