background image

Error

code

Message

Description

H02.02

Wait Config Number

Waiting For Configuration Number

Waiting for configuration parameters to be entered

Configure CN1 / CN2 depending on the output of the outdoor unit installed (CNF 

menu).

Central unit PCB replaced: heat pump not configured

H02.03

Conf Error 

Configuration Error

The configuration parameters entered are incorrect.

Configure CN1 / CN2 depending on the output of the outdoor unit installed (CNF 

menu).

H02.04

Parameter Error

Parameter Error

Restore the factory settings.

If the error is still present: change the central unit PCB.

H02.05

CSU CU mismatch

CSU does not match CU type

Software change (software number or version parameter inconsistent with the mem­

ory).

H02.07

Water Press Error 

Water Pressure Error active

Check the hydraulic pressure in the heating circuit.
Check the wiring between the central unit PCB and the pressure sensor.

Check the connection of the pressure sensor.

H02.09

Partial block 

Partial blocking of the device recognized

BL input on the central unit PCB terminal block open

Check the contact on the BL input.

Check the wiring.

Check the AP001 and AP100. parameters.

H02.10

Full Block 

Full blocking of the device recognized

BL input on the central unit PCB terminal block open

Check the contact on the BL. input.

Check the wiring.

Check the AP001 and AP100. parameters.

H02.23

System flow error 

System water flow error active

Flow problem

Insufficient flow: open a radiator valve.

The circuit is clogged:

Check that the filters are not obstructed and clean them if necessary.

Clean and flush the installation,

No circulation:

Check that the valves and thermostatic valves are open,

Check that the circulating pump is working,

Check the wiring,

Check the pump supply: if the pump does not work, replace it.

Too much air: completely vent the indoor module and the installation for optimum run­

ning.

Incorrect wiring: check the electrical connections.

Flow meter:

Check the electrical connections and the direction of the flow meter (arrow to the 

right).

Replace the flow meter if necessary

H02.25

ACI error

Titan Active System short circuited or on an open circuit

Check the connection cable.

Check that the anode has not short-circuited and is not broken.

11 Troubleshooting

7654506 - v06 - 19112019

113

Содержание MIC V200

Страница 1: ...MW 3000738 01 BAXI en Installation User and Service Manual Reversible air water Split Inverter heat pump Platinum BC iPlus V200 Smart MIC V200 ...

Страница 2: ...cal diagram 23 4 Description of the product 25 4 1 Main components 25 4 2 Control panel description 27 4 2 1 Description of the keys 27 4 2 2 Description of the display 27 4 3 Schematic diagram 30 5 Installation 33 5 1 Installation regulations 33 5 2 Standard delivery 33 5 3 Data plate 33 5 3 1 Data plate on the indoor module 34 5 3 2 Data plate on the outdoor unit 34 5 4 Respecting the distance b...

Страница 3: ... unit bus 55 5 10 10 Connecting the outdoor temperature sensor 55 5 10 11 Connecting the power supply for the electrical back up 57 5 10 12 Checking the electrical connections 57 6 Commissioning 59 6 1 General 59 6 2 Commissioning procedure with smartphone 59 6 3 Commissioning procedure without smartphone 60 6 3 1 CN1 and CN2 parameters 60 6 4 Using the installation wizard on the control panel 61 ...

Страница 4: ... 9 4 Shutdown 99 9 4 1 Switching off the heating 99 9 4 2 Stopping domestic hot water production 100 9 4 3 Shutting down the cooling function 101 9 5 Frost Protection 101 10 Maintenance 102 10 1 Precautions to be taken before maintenance operations 102 10 2 List of inspection and maintenance operations 102 10 3 Drain the appliance on the heating circuit side 103 10 4 Draining the domestic hot wate...

Страница 5: ... 3 AWHP 8 MR 2 131 14 Appendix 134 14 1 Product fiche 134 14 2 Product fiche Temperature Controls 134 14 3 Package fiche Combination heaters boilers or heat pumps 135 14 4 Package fiche Medium temperature heat pumps 136 Contents 7654506 v06 19112019 5 ...

Страница 6: ...n accordance with in stallation rules If a power supply cable comes with the appliance and it turns out to be dam aged it must be replaced by the manufacturer its after sales service or per sons with similar qualifications in order to obviate any danger If the appliance is not wired in the factory carry out the wiring by following the instructions in the Electrical connections chapter This applian...

Страница 7: ... chapter 1 2 General instructions The system must satisfy each point in the rules in force in the country that govern works and interventions in individual homes blocks of flats or other buildings Only qualified professionals are authorised to work on the appliance and the heating installation They must respect prevailing local and national regulations during fitting installation and maintenance o...

Страница 8: ... Use only original parts to replace a defective refrigeration component Use only dehydrated nitrogen for detecting leaks or for pressurised tests Do not allow the refrigerant fluid to escape into the atmosphere 1 5 Domestic water safety In accordance with safety rules a safety valve calibrated to 0 7 MPa 7 bar is mounted on the tank s domestic cold water inlet A pressure reducer not provided is re...

Страница 9: ...r unit on a solid stable structure able to bear its weight Do not install the heat pump in a place that has an atmosphere with a high salt content Do not install the heat pump in a place exposed to steam and combustion gases Do not install the heat pump in a place that may be covered in snow 1 8 Recommendations for operation The frost protection function does not work if the heat pump is switched ...

Страница 10: ...h the requirements of the various Directives applicable They are therefore delivered with the marking and any documents necessary In the interests of the quality of our products we strive constantly to improve them We therefore reserve the right to modify the specifications given in this document Our liability as manufacturer may not be invoked in the following cases Failure to abide by the instru...

Страница 11: ...omestic hot water tank volume maximum operating pressure and standby losses of the domestic hot water tank 3 Information on the electrical back up power supply and maximum output 4 Before installing and commissioning the appliance carefully read the instruction manuals provided 5 The symbol indicates compatibility with BAXI CONNECT TXM 6 Dispose of used products in an appropriate recovery and recy...

Страница 12: ...frigerant fluid connection liquid line 4 5 8 refrigerant fluid connection gas line 5 Domestic hot water flow 6 Domestic cold water inlet 7 System A flow 8 System A return 2 Symbols used 12 7654506 v06 19112019 ...

Страница 13: ...ity The unit complies with the standard type described in the EC declaration of conformity It has been manufactured and commissioned in accordance with European directives The original declaration of conformity is available from the manufacturer 3 1 2 Factory test Before leaving the factory each indoor module is tested on the following items Tightness of the heating circuit Electrical safety Tight...

Страница 14: ... 3 AWHP 8 MR 2 Cooling output kW 4 12 5 08 7 91 Energy efficiency ratio EER 4 32 4 20 4 27 Absorbed electrical power kWe 0 95 1 21 1 85 Tab 7 Common specifications Measurement type Unit AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 Total dynamic head at nominal flow rate kPa 65 55 30 Nominal air flow rate m3 h 2680 2700 3300 Power voltage of the outdoor unit V 230 230 230 Start up amperage A 5 5 5 Maximal a...

Страница 15: ...et point temperature 54 C Outside temperature 7 C Inside air temperature 20 C AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 Charging time 1 hour 40 minutes 1 hour 40 minutes 1 hour 15 minutes Domestic hot water coefficient of per formance COPDHW Cycle L 3 2 3 2 2 9 Domestic hot water coefficient of per formance COPDHW Cycle M 2 8 2 7 2 5 3 2 4 Combination heaters with medium temperature heat pump Tab 13 Tec...

Страница 16: ...d 6 35 7 24 6 19 Tj bivalent temperature COPd 1 42 1 58 1 72 Tj operation limit temperature COPd 1 42 1 58 1 72 Operation limit temperature for air to water heat pumps TOL C 10 10 10 Heating water operating limit temperature WTOL C 55 60 60 Electrical power consumption Off mode POFF kW 0 016 0 013 0 015 Thermostat off mode PTO kW 0 017 0 013 0 015 Stand by PSB kW 0 016 0 012 0 015 Crankcase heater...

Страница 17: ...dh 0 9 See The back cover for contact details 3 2 5 Sensor specifications Outdoor temperature sensor specifications Tab 14 AF60 outdoor temperature sensor Temperature C 20 16 12 8 4 0 4 8 12 16 20 24 Resistance Ω Ohm 2392 2088 1811 1562 1342 1149 984 842 720 616 528 454 Heating flow sensor specifications Tab 15 NTC heating flow sensor Temperature C 0 10 20 25 30 40 50 60 70 80 90 Resistance Ohm 32...

Страница 18: ...the second circuit is a 3 speed pump that must be set during commissioning to obtain the target flow rate in the second circuit Variable Delta P X Water flow rate l min Y Pressure available mCE 1 Circulating pump speed set to I 2 Circulating pump speed set to II 3 Circulating pump speed set to III Constant Delta P X Water flow rate l min Y Pressure available mCE 1 Circulating pump speed set to I 2...

Страница 19: ...on plate Fig 7 340 535 505 60 45 46 36 48 66 46 36 70 45 200 150 140 100 90 90 90 90 100 301 469 573 83 334 48 313 66 0 40 mm 1 2 MW 1001613 2 1 Wall bracket 2 Oscillating arm Drilling dimensions 3 Technical specifications 7654506 v06 19112019 19 ...

Страница 20: ...rcuit B return option or solar circuit flow option 2 Heating circuit B flow option or solar circuit return option 3 Refrigerant fluid connection 3 8 liquid line 4 Refrigerant fluid connection 5 8 gas line 5 Domestic hot water outlet G3 4 6 Domestic cold water inlet G3 4 7 Direct heating circuit A flow 8 Direct heating circuit A return a Adjustable feet 3 Technical specifications 20 7654506 v06 191...

Страница 21: ...frigerant fluid connection 2 1 2 refrigerant fluid connection 3 3 4 AWHP 6 MR 3 Fig 10 23 2 1 2 99 5 164 5 492 193 5 3 5 4 3 360 330 32 5 300 40 404 5 48 22 3 630 320 8 5 809 500 310 154 5 62 MW 1000919 1 1 1 4 refrigerant fluid connection 2 1 2 refrigerant fluid connection 3 Technical specifications 7654506 v06 19112019 21 ...

Страница 22: ...R 2 Fig 11 943 950 45 56 53 28 19 23 417 175 330 370 30 443 447 175 65 42 2 A B MW M001442 2 1 1 3 8 refrigerant fluid connection 2 5 8 refrigerant fluid connection 3 Technical specifications 22 7654506 v06 19112019 ...

Страница 23: ...H PUMP A 7715087 Condensation sensor H M I 230V LOW NOISE 7714998 230V 85554908 7717537 3 Way Valve DHW ON OFF Electrical back up 7726152 7740282 Sensor Solar Panel Sensor Solar Tank R0 N N L PUMP S1 S2 1234 SOLAR 7717996 7724255 Tab 17 Electrical diagram legend ACI BDR Option Impressed current anode option BL1 Multifunction BL1 multifunction input BL2 Multifunction BL2 multifunction input BLUETOO...

Страница 24: ...ture sensor SENSOR SOLAR TANK Domestic hot water tank temperature sensor SENSOR TARGET Water temperature sensor on the plate heat exchanger outlet So So Energy counter Electrical energy meter SOLAR PCB for controlling a solar circuit option S2 S3 Bus for communicating with the outdoor unit Tdhw Domestic Hot Water t Domestic hot water temperature sensor Tout Outside temperature sensor Outdoor tempe...

Страница 25: ...tanium anode 11 Mechanical pressure gauge 12 Air vent 13 Three way valve with reversal motor for heating domestic hot water 14 3 kW electrical back up 15 Heat exchanger for the production of domestic hot water in the tank coil 16 Main circulating pump 17 Magnetic filter 18 Heating circuit safety valve 3 bar 19 Disconnector 20 Thermostatic mixing valve Fig 13 MIC V200 MW 3000654 2 5 4 6 7 8 1 3 9 1...

Страница 26: ...sure gauge 3 DHW circuit safety valve 4 Electric panel 5 User interface 6 ON OFF button 7 Flow meter 8 Plate heat exchanger condenser 9 Expansion vessel 10 Magnesium anode or optional titanium anode 11 Mechanical pressure gauge 12 Air vent 13 Three way valve with reversal motor for heating domestic hot water 14 Electrical back up 15 Heat exchanger for the production of domestic hot water in the ta...

Страница 27: ...n of the keys 1 h back to the previous level without saving the modifications made manual reset 2 accessing the heating parameters lowering the value 3 accessing the domestic hot water parameters raising the value 4 MODE display accessing the menu selected or confirming the value modification 4 2 2 Description of the display Hydraulic back up Hydraulic back up in demand Electrical back up Stage 1 ...

Страница 28: ...dy symbol cooling mode on Flashing symbol cooling request pending Menu display Information menu displays the measured values and the statuses of the appliance User menu provides access to the User level setting parameters Installer menu provides access to the Installer level setting parameters Manual Forcing menu the appliance runs at the set point displayed the pumps operate and the three way val...

Страница 29: ...r program for Thursday Timer program for Friday Timer program for Saturday Timer program for Sunday CLOCK sub menu CLK Temperature sensors Room temperature sensor connected fixed symbol for WINTER mode flashing symbol for SUMMER mode Outside temperature sensor connected fixed symbol for WINTER mode flashing symbol for SUMMER mode Other Information Test Menu forced operation in heating and cooling ...

Страница 30: ...ting circuit MW 3000700 01 P Q T T T T A4 A3 A1 A2 D T AB B A A A1 Domestic hot water outlet A2 Domestic cold water inlet A3 Direct heating circuit A return A4 Direct heating circuit A flow D Disconnector 4 Description of the product 30 7654506 v06 19112019 ...

Страница 31: ... A B T AB B A AB A B A1 A2 A4 B1 B2 A3 D A1 Domestic hot water outlet A2 Domestic cold water inlet A3 Direct heating circuit A return A4 Direct heating circuit A flow B1 Mixed heating circuit B flow B2 Mixed heating circuit B return D Disconnector 4 Description of the product 7654506 v06 19112019 31 ...

Страница 32: ... S S S1 A4 E Solar circuit A1 Domestic hot water outlet A2 Domestic cold water inlet A3 Direct heating circuit A return A4 Direct heating circuit A flow S1 Solar circuit heating return S2 Solar circuit heating flow Buffer tank Solar circuit buffer tank D Disconnector 4 Description of the product 32 7654506 v06 19112019 ...

Страница 33: ... bag containing the outdoor temperature sensor the key for maintenance operations on the magnetic filter one 5 8 nut for the refrigeration connection a second Bluetooth label an energy label one bag of screws gaskets cable clamps Connection plate A connection plate Two 800 mm long 3 8 and 5 8 refrigeration hoses A condensate collector box with hose A mounting jig with instructions One screw bag 5 ...

Страница 34: ... ence C Maximum number of el bows AWHP 4 5 MR 2 to 30 m 30 m 10 AWHP 6 MR 3 2 to 40 m 30 m 15 AWHP 8 MR 2 2 to 40 m 30 m 15 2 Make one or two horizontal loops with the refrigerant connections to reduce disruption If the length of the refrigerant connections is less than 2 m disruptions can occur Functional disruptions caused by a fluid overload Noise pollution caused by the circulation of the refr...

Страница 35: ...iling and the top of the product is less than 250 mm it will not be possible to remove the anode for maintenance operations In this case replace the magnesium anode with the impressed current anode option package EH921 before positioning the product 5 5 3 Install the indoor module in a cupboard The indoor module can be installed in a cupboard Observe the overall dimensions including hinges of 564 ...

Страница 36: ...n the expansion vessel to access the feet at the rear of the appliance 2 Remove the expansion vessel 3 Unscrew the feet using an Allen key 4 Use a spirit level to check that the appliance is completely level 5 Refit the expansion vessel in its housing and close the hook to immobilise the vessel 5 5 7 Attaching the indoor module to the wall To prevent the indoor module from tipping over we recommen...

Страница 37: ...se the maximum circuit temperature in heating mode or failing this at a minimum of 55 C If the volume of the integrated expansion vessel 12 l is not sufficient add an external expansion vessel on the heating circuit Volume of the expansion vessel Tab 20 Underfloor heating type installation maximum temperature of 40 C Static height Expansion vessel inflation valve pres sure Volume of the expansion ...

Страница 38: ...er operating pressure The tanks on our domestic hot water heaters can run at a maximum operating pressure of 1 0 MPa 10 bar The recommended operating pressure is under 0 7 MPa 7 bar 5 6 3 Connecting the various circuits The water connections are made on the connection plate 1 Tighten the various connectors between the indoor module and the connection plate 5 6 4 Fitting the condensate collector bo...

Страница 39: ...sion vessel s is sufficient for the volume of water in the heating installation 2 Check the inflation pressure of the expansion vessel s 3 Check that the heating circuit contains adequate water If necessary top up with more water 4 Check that the water connections are properly sealed 5 Check that the heating circuit has been correctly purged 6 Check that the filters are not clogged Clean them if n...

Страница 40: ...rcuits on the connection plate 2 Open the air vents 3 Open the disconnector valve to the FILL position to start filling 4 Monitor the pressure on the mechanical pressure gauge Important The mechanical pressure gauge is located to the right of the control panel and is only used when filling the indoor module with water After the heat pump is started on the pressure is shown on the display 5 When th...

Страница 41: ...gas the domestic hot water tank and the distribution network in order to eliminate noises and hammering caused by trapped air moving in the pipes during draw off 8 Check the safety devices particularly the safety valve or safety unit referring to the instructions provided with those components Domestic water quality In regions where the water is very hard Th 20 fH 11 dH we recommend fitting a soft...

Страница 42: ...thing must obstruct the free circulation of air around the outdoor unit intake and outlet Close to sleep zones Close to a terrace Opposite a wall with windows 4 Ensure the support meets the following specifications Specifications Examples Flat surface that can support the weight of the outdoor unit and its ac cessories Concrete base Sill Concrete blocks No rigid connection to the building served t...

Страница 43: ...wing conditions Fig 50 MW 6000252 2 1 2 3 4 1 Install the outdoor unit sufficiently high off the ground to allow condensates to be discharged correctly 2 Ensure the base meets the following specifications Specifications Reason Maximum width equal to the width of the outdoor unit Height at least 200 mm greater then the average depth of the covering of snow This helps to protect the exchanger from s...

Страница 44: ...he refrigerant load is in excess of 5 tonnes of CO2 equivalent or when a refrigerant connection is necessary the case with split systems even when fitted with a quick coupling device 1 Install the refrigerant connection pipes between the indoor module and the outdoor unit For connection on the lower section use the refrigerant hoses supplied with the appliance For connection on the upper section u...

Страница 45: ...s watertight 3 Fitting the connections Important Use the original nuts or discard these depending on the outdoor unit installed Use the copper gaskets with the adapters from the package EH146 4 Bead the pipes Fig 52 Fitting refrigerant hoses MW 3000741 01 5 8 3 8 L 800mm Fig 53 MW 3000742 2 Pfffff 1 2 Tab 24 Fig A Fig B AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 Discard the original nuts Use the adapters...

Страница 46: ...panner so as not to twist the internal pipe 1 Do not use a spanner on this part of the valve there is a danger of the refrigerant leaking 2 Recommended position of the spanners for tightening the nut 3 Thread the nuts onto the pipes 4 Bead the pipes 5 Apply refrigerant oil to the beaded parts to facilitate tightening and improve the seal 6 Connect the pipes and tighten the nuts with a torque wrenc...

Страница 47: ...emove air and moisture from the refrigerant circuit 1 Check that the A and B C stop valves are closed 2 Connect the vacuum gauge and the vacuum pump to the service connection on A stop valve 3 Produce a vacuum in the indoor module and the refrigerant connection pipes 4 Check the pressure according to the recommendations table below Tab 27 Outdoor temperature C 20 10 0 10 Pressure to be reached Pa ...

Страница 48: ...ve using a safety loader Caution Prevent oil traps If the pipes are not connected immediately plug them to prevent moisture from entering Tab 28 Quantity of refrigerant fluid to be added Length of refrigeration pipe 7 m 10 m 15 m 20 m 30 m Yg m AWHP 4 5 MR 1 0 0 045 kg 0 120 kg 0 195 kg 0 345 kg 15 2 1 The outdoor unit is pre charged with 1300 kg of refrigerant fluid 2 Calculation Xg Yg m x pipe l...

Страница 49: ...ce via a circuit that includes an omnipolar switch with contact opening distance of 3 mm or more Single phase models 230 V 6 10 50 Hz When making electrical connections to the mains respect the following polarities Tab 30 Colour of the wire Polarity Brown wire Live Blue wire Neutral Green yellow wire Earth Caution Secure the cable with the cable clamp provided Be careful that you do not invert any...

Страница 50: ...16 13 AWHP 8 MR 2 Single phase 3 x 4 25 17 1 Connection cable linking the outdoor unit to the indoor module 5 10 3 Accessing the PCBs 1 Unscrew the two screws on the protective cover for the PCBs but do not remove them 2 Slide the cover upwards and remove it 3 Lift the control panel flap slightly 4 Tilt the control panel flap forwards For more information see Removing the appliance s front panel p...

Страница 51: ...on inputs So So Electric energy meter Condensation Condensation sensor X13 Option ACI BDR X17 Not used X18 Input output for the HPC 01 PCB X19 Optional connection cable for Silent mode X22 Bus for communication with the HPC 01 PCB X23 Bus for communicating with the outdoor unit X24 230 V 50 Hz power supply X25 Heating Domestic hot water directional valve X26 Pump only if connecting a buffer tank X...

Страница 52: ...hermostat Tout Do not connect anything Tflow Flow sensor X8 L Bus to the EHC 06 PCB X9 L Bus terminal connector PCB terminal block for the solar option 1 S1 solar collector temperature sensor S2 domestic hot water tank temperature sensor 2 Solar circuit circulating pump 3 230 V power supply Fig 64 MW 3000557 03 X8 X9 X3 X2 X1 FUSE SW2 X6 Fig 65 MW 1001569 1 R0 N N L S1 S2 1 2 3 5 Installation 52 7...

Страница 53: ... Danger of electric shock the length of the conductors between the traction arrester device and the terminal blocks must be such that the active conductors are put under tension before the earth conductor 5 10 7 Connecting the indoor module The power supply for the indoor unit is prewired in the factory 1 Connect the standby power supply cable at the rear of the appliance to the installation s ele...

Страница 54: ... and L wires 4 Secure the screw with the earth wire on the chassis Ensure that the earth wire is correctly placed under the washer in contact with the chassis 5 Connect the other wires to the appropriate terminals 6 Feed the cable into the cable duct and adjust the length of the cable accordingly Lock it in position using the traction arrester device 7 Put the service panel back in place Connectin...

Страница 55: ...he earth wire must be 10 mm longer than the N and L wires 3 Feed the cable into the cable duct and adjust the length of the cable accordingly Lock it in position with a cable clamp 4 Put the service panel back in place 5 10 9 Connecting the outdoor unit bus 1 Connect the outdoor unit bus between the S2 and S3 terminals on the X23 connector in the indoor module s EHC 06 central unit PCB 2 Position ...

Страница 56: ...crews provided diameter 4 mm 4 Connect the cable to the outdoor temperature sensor Recommended positions Place the outside sensor in a position that covers the following characteristics On a façade of the area to be heated on the north if possible Half way up the wall of the area to be heated Under the influence of changes in the weather Protected from direct sunlight Easy to access Fig 75 MW 8800...

Страница 57: ...rical back up power supply cable into the cable duct reserved for the 230 V circuit cables 2 Connect the cable to the terminal block as shown in the figure Press the push button to allow the wire to be correctly inserted in the connector and locked 1 Live L 2 Neutral 3 Earth 5 10 12 Checking the electrical connections 1 Check the mains electricity connection to the following components Outdoor uni...

Страница 58: ...of the sensors Room temperature sensor if present Outdoor temperature sensor Flow sensor for the second circuit if present 5 Check the connection of the circulating pump s 6 Check that the wires and terminals are properly tightened or connected to the terminal blocks 7 Check the separation of the power and safety extra low voltage cables 8 Check the connection of the underfloor heating safety ther...

Страница 59: ...on to help you commission and configure the parameters for the heating installation 1 Download the application Baxi START on Google Play or on the App Store 2 Follow the application s instructions on the smartphone for commissioning and configuring the heating installation To establish a Bluetooth connection between the smartphone and the heat pump use the information indicated on the label locate...

Страница 60: ...lation They can be used to preconfigure the parameters based on the installation configuration 6 The heat pump begins the vent cycle Points to check After commissioning domestic hot water production takes priority Keep this operating mode to increase the temperature and check that the heat pump is operating correctly At the end of the vent cycle if the heat pump does not start check the flow tempe...

Страница 61: ...heating circuit with mixing valve 04 One direct underfloor heating circuit 05 One direct underfloor heating circuit and one domestic hot water tank 06 4 Confirm the selection by pressing the key 5 Set the heating curve The main parameters are set 6 Apply the required settings based on the additional options connected 6 5 Checking the minimum flow of the direct circuit Heating installations must be...

Страница 62: ...g and domestic hot water functions are then no longer guaranteed 1 Set circuit A to frost protection mode to shut down the heating demand The circulating pump for circuit A is shut down If necessary disconnect the power supply of the pump to ensure it shuts down 2 Create a heating demand on circuit B 3 Check that the mixing valve is fully open by pushing the white tab fully upwards 4 Check the wat...

Страница 63: ...hut down the heat pump and carry out the following operations After about 10 minutes vent the air in the heating system Check the hydraulic pressure on the user interface If necessary top up the water level in the heating system Check the fouling level of the filter s present both in the heat pump and on the installation If necessary clean the filter s 5 Restart the heat pump 6 Explain how the sys...

Страница 64: ...Modify the value of the parameter using the and keys 9 Confirm the new value of the parameter by pressing the key 10 Go back to the main display by pressing the h key 7 2 Installer menu Fig 89 1 2 MW 1000753 1 3 2 1 Sub menu available 2 Name of the PCB or circuit 3 Setting parameters Tab 38 List of Installer sub menus Important Only the parameters used by the device are described in this manual Su...

Страница 65: ...t in reduced mode that allows switching to comfort mode Can be set from 5 C to 30 C 16 16 CP210 Comfort footpoint of the temperature of heat curve of the circuit can be set from 16 to 90 C set to 15 the curve base temperature is set automatically and is the same as the room set point temperature 15 15 CP220 Reduced footpoint of the temperature of heat curve of the circuit can be set from 6 to 90 C...

Страница 66: ... CP560 Configuration of the Domestic Hot Watter Antilegionnella Protection of the zone not availa ble 0 CP600 Heat demand setpoint during process heat of zone not availa ble 60 CP610 Hysteresis switched on for process heat per zone not availa ble 6 CP620 Hysteresis switched off for process heat per zone not availa ble 6 CP630 Startday of the function antilegionella of the zone not availa ble 6 CP6...

Страница 67: ...ne Can be set from 0 to 100 Do not modify this setting 100 CP530 Pulse Width Modulation pump speed per zone Can be set from 20 to 100 Do not modify this setting 100 CP730 Selection of heat up speed of the zone 0 Extra Slow 1 Slowest 2 Slower 3 Normal 4 Faster 5 Fastest Do not modify this setting 2 CP740 Selection of cool down speed of the zone 0 Slowest 1 Slower 2 Normal 3 Faster 4 Fastest Do not ...

Страница 68: ... setting DP004 Legionella mode protection calorifier 0 Disabled 1 on the domestic hot water tank is superheated to 65 C for 20 minutes once a week 2 automatic the domestic hot water tank is remotely controlled 0 DP046 Maximum domestic hot water temperature Can be set from 10 C to 70 C 70 DP047 Maximum duration of the domestic hot water production Can be set from 1 to 10 hours 3 4 5 kW 6 kW 8 kW 2 ...

Страница 69: ...e indicating that pressure is low Can be set from 0 bar to 2 bar 0 8 not available AP063 Maximum central heating flow temperature setpoint Can be set from 20 C to 75 C Electrical back up 75 not available AP073 Outdoor temperature upper limit for heating 22 22 AP075 Temperature variance from set outdoor upper temp limit in which the generator will not heat or cool Can be set from 0 to 10 C 4 4 AP07...

Страница 70: ... 99 runs continuously 3 ADV ADV advanced parameters not available AD Auto detect available CNF Reset factory parameters See the data plate 7 2 6 Installer EHC 06 and SCB 04 ADV menu AP Appliance Parameters Appliance parameters ADV Description of the ADV advanced parameters Factory setting EHC 06 Factory setting SCB 04 AP006 Appliance will report low water pressure below this value Can be set from ...

Страница 71: ...be set from 0 Min to 600 Min 20 HP031 Delay time for stopping the backup energy source for the heating circuits Can be set from 0 Min to 600 Min 0 auto mode use parameters HP047 to HP050 4 HP033 Value of the pulse coming from the electrical counter Can be set from 0 Wh to 1000 Wh 1 HP047 Delay for starting the backup when the outdoor temp is equal to the parameter Max Outdoor T backup Can be set f...

Страница 72: ... be set from 0 to 30 C 0 HP094 Start time of the heat pump low noise function Can be set from 00 00 to 23 59 Value accepted when HP058 1 22 00 HP095 End time of the heat pump low noise function Can be set from 00 00 to 23 59 Value accepted when HP058 1 06 00 HP108 Activation time delays for the back ups between stage 1 and stage 2 electrical back up in central heating mode 4 PP016 Maximum central ...

Страница 73: ...arameters by pressing the or key 5 Select the CNF menu control panel reset by pressing the or keys 6 Confirm by pressing the key 7 Enter the values corresponding to the type of outdoor unit and the type of back up by pressing on the or key Important The CN1 and CN2 values are indicated on the appliance s data plate 8 Confirm the selection by pressing the key 9 Go back to the main display by pressi...

Страница 74: ...ctrical energy consumption function Tab 48 Connections The electrical energy meter is connected to the S0 S0 input on the EHC 06 PCB Do not install meters for the electrical back ups Energy meter specifications Minimum power supply voltage range 24 V 10 Minimum admissible intensity 20 mA Minimum pulse time 25 ms Maximum frequency 20 Hz Pulse weight between 1 and 1000 Wh If the meter pulse weight i...

Страница 75: ...ack up is fitted Set the HP034 and HP035 parameters according to the configuration of the electrical back up stages output 7 3 5 Configuring a convection fan or underfloor cooling This function is only available when the type of circuit selected is underfloor heating or a convection fan CP020 parameter set to 2 or 5 Important The heating should be activated in order for cooling to function 1 Go to...

Страница 76: ...tion and deactivates all other control system functions When the screed drying function is active on one circuit all other circuits and the domestic hot water circuit continue to run It is possible to use the screed drying function on circuits A and B The parameter settings must be made on the PCB that controls the circuit concerned Screed drying curve 1 Number of days 2 Heating set point temperat...

Страница 77: ...d to add the flexibility of using several types of on off thermostat or OT Tab 53 Control parameter for the OT input on the R Bus terminals Parameter Description CP640 Configuration of the contact direction of the OT input for heating mode CP690 Reversal of the direction of the logic in cooling mode compared to heating mode Tab 54 Default settings for the CP640 and CP690 parameters Value of the CP...

Страница 78: ...nd 0 0 Open Heating Heating demand No heating demand 0 0 Closed Cooling Cooling demand No cooling demand 7 3 10 Setting the parameters for using photovoltaic energy When lower cost electrical energy is available such as photovoltaic energy the heating circuit and domestic hot water tank if present can be overheated Underfloor cooling cannot be supplied with power in this way 1 Activate overheating...

Страница 79: ... Grid signals 3 Choose the contact directions of the BL1 IN and BL2 IN multifunction inputs by setting the AP098 and AP099 parameters Tab 57 Parameter Description AP098 Configuration of the BL1 contact direction 0 input active on open contact 1 input active on close contact AP099 Configuration of the BL2 contact direction 0 input active on open contact 1 input active on close contact 4 Configure t...

Страница 80: ... is running 7 4 COUNTERS TIME PROG CLOCK menus Tab 60 List of sub menus Sub menu Description CNT COUNTERS CIRCA Timer programming for the main heating circuit CIRCB Timer programming for the additional heating circuit B DHW Timer programming for the domestic hot water circuit CLK Setting the clock and the date 7 4 1 COUNTERS TIME PROG CLOCK CNT menus Tab 61 Choosing the menu Counters Selection Cir...

Страница 81: ... of compressor operating hours hours X CODE Enter the installer code to access the following pa rameters X AC002 Number of hours that the appliance has been producing energy since last service hours X AC003 Number of hours since the previous servicing of the appliance hours X AC004 Number of heat generator starts since the previous servicing X AC013 Seasonal coefficient of performance X SERVICE Re...

Страница 82: ... set to 0 the activation and deactivation time delays on the back up are set according to the outdoor temperature In heating mode the back up is managed by the following parameters Tab 65 Parameter for heating production Parameter Description AP016 Activate or deactivate processing of the heating demand for central heating HP030 Start up time delay for the next back up generator in central heating...

Страница 83: ...es full protection of the system by starting up the back ups if necessary Additional protection is provided if the water temperature falls too sharply In this case the outdoor unit is shut down Operating principle when the outside temperature falls below the operating threshold of the outdoor unit If the outside temperature is below the minimum operating temperature of the outdoor unit as defined ...

Страница 84: ...uce the maximum duration of domestic hot water production 2 Heating only Production of domestic hot water is off Even if the domestic hot water set point is not reached a minimum heating period is forced This period can be adjusted and defined with the DP048 parameter After the heating period tank loading is again enabled 3 Domestic hot water production only When the domestic hot water set point i...

Страница 85: ... or sensors actually connected Tab 69 Choosing the menu Counters Selection Measured values on circuit A Choose the EHC 06 menu Measured values on circuit B Choose the SCB 04 menu Measured values connected to the operation of the heat pump Choose the EHC 06 menu Tab 70 Values available X in the sub menus EHC 06 SCB 04 Parameter Description Unit EHC 06 SCB 04 AM002 Silent mode status X AM010 The cur...

Страница 86: ...6 SCB 04 Fxx xx HMI software version X X Pxx xx HMI parameter version X X 7 6 1 Control system sequence Tab 72 List of statuses and sub statuses Status Appliance AM012 parameter Appliance sub status AM014 parameter 0 00 total system shut down 1 heating cooling domestic hot water de mand Heat Demand 00 off The set point is reached The compressor can start up whenever necessary 01 anti short cycle T...

Страница 87: ... maximum operat ing temperature The compressor has stopped The back ups are operating 68 the hybrid function requests compressor shut down The compressor has stopped The back ups are operating 69 defrosting running The compressor is running 70 defrosting conditions not met The compressor has stopped The back ups are operating 71 defrosting running The compressor and the back ups are running 88 BL ...

Страница 88: ...defrosting running The compressor is running 70 defrosting conditions not met The compressor has stopped The back ups are operating 71 defrosting running The compressor and the back ups are running 88 BL Back up limited Back ups shed 89 BL Heat pump limited Compressor shed 90 BL Heat pump back up limited Compressor and back ups shed 91 BL Off peak rate Off peak cost 92 PV with Heat pump Photovolta...

Страница 89: ...oint limited If the heating set point on the heat pump differs from the system set point 60 pump post operation Heat pump and back up shut down system pump running 65 compressor bypass The back ups are operating 66 the temperature exceeds the compressor s maximum operating tempera ture The compressor has stopped The back ups are operating 67 the outside temperature is lower than the compressor s m...

Страница 90: ...e exceeds the compressor s maximum operating tempera ture The compressor has stopped The back ups are operating 67 the outside temperature is lower than the compressor s maximum operat ing temperature The compressor has stopped The back ups are operating 68 the hybrid function requests compressor shut down The compressor has stopped The back ups are operating 69 defrosting running The compressor i...

Страница 91: ...itions not met The compressor has stopped The back ups are operating 71 defrosting running The compressor and the back ups are running 17 DeAiration 30 normal operation The compressor or the back ups are running 31 internal set point limited If the heating set point on the heat pump differs from the system set point 60 pump post operation Heat pump and back up shut down 65 compressor bypass and ba...

Страница 92: ...o the EHC 06 PCB respecting the 230 400 V and 0 40 V cable feed throughs 2 On initial start up or after a reset of the factory parameters set the CN1 and CN2 parameters according to the output of the outdoor unit 3 Select the number corresponding to the installation type by pressing the or key Installation type No 1 direct underfloor heating 1 domestic hot water tank 06 Selecting the installation ...

Страница 93: ...ne underfloor heating circuit Fig 106 MW 1001547 2 CIRC A CIRC B 9 5 2 6 10 11 3 4 SCB 04 X6 X8 X9 X7 10 X23 X28 1 7 8 EHC 06 X12 X27 M M BUS 230V 50Hz 230V 50Hz 230V 50Hz 1 3 7 8 2 4 5 6 BAXI 9 HPC 01 EH916 EH917 8 Connection and installation examples 7654506 v06 19112019 93 ...

Страница 94: ...options to the SCB 04 PCB respecting the 230 400 V and 0 40 V cable feed throughs 3 On initial start up or after a reset of the factory parameters set the CN1 and CN2 parameters according to the output of the outdoor unit 4 Select the number corresponding to the installation type by pressing the or key Installation type No 1 direct heating circuit 1 underfloor heating circuit 1 domestic hot water ...

Страница 95: ...ar circuit Fig 107 MW 3000755 2 X23 X12 X28 1 7 8 EHC 06 9 HPC 01 R0 N N L S1 S2 1234 SOLAR CIRC A CIRC B M Strateo_F0002 BUS 230V 50Hz 230V 230V 50Hz 50Hz 230V 50Hz 9 2 3 6 2 1 8 7 HA255 EH919 5 4 5 4 BAXI 8 Connection and installation examples 7654506 v06 19112019 95 ...

Страница 96: ... the domestic hot water sensor S2 is greater than ΔT factory setting 4 K The solar primary pump is shut down when one of the following conditions is fulfilled Domestic hot water temperature S2 equal to the setpoint B Temperature difference between the solar circuit flow sensor S1 and the domestic hot water sensor S2 is less than ΔT 1 6 factory setting 4 K 1 6 8 4 Installation with a swimming pool ...

Страница 97: ...essing the and keys 3 Confirm access by pressing the key 4 Access the circuit B and SCB 04 PCB parameters by pressing the or key 5 Confirm the selection by pressing the key 6 Configure the following parameters Tab 73 Heating configuration for a swimming pool Parameter Description Value to be set CP020 Circuit type 3 CP540 Swimming pool water temperature set point 26 C Important Back up operation f...

Страница 98: ...enu CLOCK sub menu PCB selection menu Important The icon is displayed only if an optional PCB has been installed Important The different menus are only accessible when the icons flash Press the key to access the next menu access the next sub menu access the next parameter increase the value Press the key to access the previous menu access the previous sub menu access the previous parameter decreas...

Страница 99: ...est of the manual 9 3 Start up 1 Switch on the outdoor unit and the indoor module 2 The heat pump begins its start up cycle If the start up cycle runs normally an automatic venting cycle is initiated Otherwise an error message is displayed 9 4 Shutdown 9 4 1 Switching off the heating Important Heating mode can be managed via the TIME PROG sub menu dedicated to timer programming Important If the he...

Страница 100: ... sub menu dedicated to timer programming 1 Go to stop mode by pressing the key 2 Select domestic hot water production mode pressing the key 3 Confirm by pressing the key 4 Select domestic hot water production shut down by pressing the key The screen displays The frost protection function continues to run Production of domestic hot water has been shut down Important Press the key to restart the app...

Страница 101: ...ram to stop cooling 9 5 Frost Protection If the temperature of the heating water in the heat pump falls too much the integrated protection device switches itself on This device functions as follows If the water temperature is lower than 5 C the circulating pump starts up If the water temperature is lower than 3 C the back up starts up If the water temperature is higher than 10 C the back up shuts ...

Страница 102: ...Before any work switch off the mains electricity to the heat pump and the electrical back up if present Danger of electric shock Check the discharge from the capacitors of the outdoor unit 10 2 List of inspection and maintenance operations Tab 75 Checking the operation of the installation Check Heat pump and back up in heating mode Heat pump in cooling mode Heat pump in convection fan mode User in...

Страница 103: ...Casing Clean the outside of the appliance using a damp cloth and a mild detergent For more information see Clean the magnetic sieve filters page 104 Checking the minimum flow of the direct circuit page 61 Setting the flow rate of the second circuit page 62 Cleaning the plate heat exchanger page 107 Checking the magnesium anode page 107 10 3 Drain the appliance on the heating circuit side The heati...

Страница 104: ...ing circuit return if present prevent the plate heat exchanger from becoming clogged The magnetic filters must be cleaned every year to ensure that water is able to flow correctly within the installation 10 5 1 Magnetic filter annual maintenance 1 Switch off the appliance and close the valves for the heating circuits on the plate 2 Remove the magnet from the filter The magnetic particles stuck ins...

Страница 105: ... in the installation If the flow rate is too low clean the filter fully For more information see Checking the minimum flow of the direct circuit page 61 Setting the flow rate of the second circuit page 62 10 5 2 Full cleaning of the magnetic filter If the flow rate in the installation is too low fully clean the magnetic filter This operation requires the appliance to be fully drained 1 Power off t...

Страница 106: ...he handling tool provide in the accessories bag 6 Disassemble the different parts of the mud pot The magnetic particles stuck inside the filter will drop to the bottom 7 Clean the different parts with clean water 4 MW 1001311 1 5 MW 1001578 1 6 MW 1001313 1 7 MW 1001314 1 10 Maintenance 106 7654506 v06 19112019 ...

Страница 107: ...ntinues to provide the required performance 1 Isolate the exchanger by closing the two valves 2 Unscrew the plate heat exchanger on the domestic hot water circuit side 3 Clean the plate heat exchanger 10 7 Checking the magnesium anode The condition of the anode must be checked after the first year then at least every 2 years After the first inspection the check may be performed each year based on ...

Страница 108: ...ws in criss cross pattern using a torque wrench Important Torque 12 N m 11 Reopen the water inlet valves 10 8 Check the hydraulic pressure If the hydraulic pressure of your heating system installation is too low or too high malfunctions and faults may appear Recommended hydraulic pressure from 1 5 bar to 2 bar 1 Check the hydraulic pressure shown alternately on the control panel 2 If the hydraulic...

Страница 109: ... the control panel If the indoor module is switched off the control panel battery takes over to keep the correct time The battery must be replaced when the time is no longer saved To replace the battery remove the appliance s front panel to allow access to the interior of the control panel 1 Unscrew the two screws on the protective cover for the PCBs but do not remove them 2 Slide the cover upward...

Страница 110: ... by pushing it gently forwards 6 Insert a new battery Important Battery type CR2032 3V Do not use rechargeable batteries Do not discard used batteries in the dustbin Take them to an appropriate collection place 7 Re assemble everything Fig 130 MW 3000663 01 4 3 Fig 131 Remove the battery MW 3000475 01 10 Maintenance 110 7654506 v06 19112019 ...

Страница 111: ... panel of the indoor module and the protective cap 6 Switch the mains supply to the indoor module and the electrical back up immersion heater back on 11 2 Error messages The message appears when a fault code is detected After resolving the problem pressing the key resets the appliance s functions and thus eradicates the fault If several faults occur they are displayed one after the other 1 Reset t...

Страница 112: ... range Check the wiring between the central unit PCB and the sensor Check that the sensor has been fitted properly Check the Ohmic value of the sensor Replace the sensor if necessary H00 48 THp Flow Closed Heat pump flow temperature sensor is either shorted or measures a temperature above range Check the wiring between the central unit PCB and the sensor Check that the sensor has been fitted prope...

Страница 113: ...CB terminal block open Check the contact on the BL input Check the wiring Check the AP001 and AP100 parameters H02 10 Full Block Full blocking of the device recognized BL input on the central unit PCB terminal block open Check the contact on the BL input Check the wiring Check the AP001 and AP100 parameters H02 23 System flow error System water flow error active Flow problem Insufficient flow open...

Страница 114: ...wiring between the central unit PCB and the communication bus on the outdoor unit Check the connection of the communication cable between the central unit PCB and the interface PCB Check the connection of the supply cable between the central unit PCB and the in terface PCB Check the connection of the outdoor unit supply cable 11 2 2 Fault codes If a fault code is still present after several automa...

Страница 115: ...properly open also check the hydroblock Completely vent the indoor module and the installation for optimum running Incorrect wiring check the electrical connections Flow meter Check the electrical connections and the direction of the flow meter arrow to the right Replace the flow meter if necessary 11 2 3 Alarm codes An alarm code is a temporary heat pump status resulting from the detection of an ...

Страница 116: ...u opens the row of the error in the memory appears briefly The PCB name appears Go back to the error list by pressing the h key Important The errors are stored from the most recent to the oldest 6 Go back to the Er xxx display by pressing the h key Press the key the CLR parameter flashes after the errors 000 corresponds to the PCB selected Clear the error memory by pressing the key 7 Exit the Malf...

Страница 117: ...ried out by a qualified professional in accordance with prevailing local and national regulations 1 Switch off the heat pump 2 Cut the mains supply to the heat pump 3 Recover the refrigerant fluid in accordance with prevailing regulations Important Do not allow the refrigerant fluid to escape into the atmosphere 4 Disconnect the refrigerant connections 5 Close the water mains 6 Drain the installat...

Страница 118: ...te collector box 3 7602241 PVC elbow hose 4 7716416 G1 vent valve 5 7716415 G3 4 vent valve 6 7674854 G1 lock nut 7 V139826 G3 4 lock nut 8 95013062 Green gasket 30 x 21 x 2 9 95013060 Green gasket 24 x 17 x 2 10 94914302 CV18 DN15 non return valve 11 7723197 L800 3 8 M F refrigerant hose 12 7704509 L800 5 8 M F refrigerant hose 13 300024031 Retaining clip 13 Spare parts 118 7654506 v06 19112019 ...

Страница 119: ... 3 1 4 3 7 7 6 8 6 10 20 19 13 9 12 13 13 21 16 11 14 18 17 4 2 3 14 15 5 23 22 Tab 82 List of spare parts for the casing Markers Reference Description 1 7717363 Upper panel 2 7697545 Rear panel 13 Spare parts 7654506 v06 19112019 119 ...

Страница 120: ... for indoor unit 12 7704215 Complete frame 13 97860646 Adjustable foot M10 x 35 14 7676037 Wheel 15 7616968 Expansion vessel 12 l 16 7743221 MIC V200 tank 17 7749464 Inspection hatch anode gasket screw assembly 18 200021542 Ø 40 410 mm long magnesium anode 19 95014035 Ø 35 x 8 5 x 2 gasket 20 94974527 Nylon spacer 21 89604901 Anode earthing wire 22 95013134 Lip gasket Ø 122 23 7740411 Insulation t...

Страница 121: ...2 EHC 06 PCB 4 7632095 Green 2 pin BUS connector 5 7632096 White 2 pin connector 6 200009965 Orange 2 pin connector 7 7674749 White 3 pin connector 8 96568001 Finder relay 220 V 30 A 9 300024354 Clip on cable bracket 10 7696573 PCB cover 11 300020013 Clip on interface PCB bracket series 100 2 12 7653678 HPC 01 PCB 13 7722701 Terminal block 14 7704981 Control panel bracket 15 7722668 Safety thermos...

Страница 122: ...t 22 7646220 Grey HMI bracket 23 7675263 Power supply button 24 S62733 G1 4 0 4 bar pressure gauge 25 7715094 SMART PCB 26 7658838 MK2 HMI display 27 7697269 Power supply switch support 28 7724467 PCB bracket 29 7697544 HMI bracket 30 95362450 Outdoor temperature sensor 31 300009070 Outdoor temperature sensor connector 32 7214943 Terminal connector 13 Spare parts 122 7654506 v06 19112019 ...

Страница 123: ... 12 18 21 4 16 24 52 35 36 6 9 13 23 56 55 36 41 40 35 39 26 34 26 12 34 26 12 34 36 15 49 17 5 37 28 8 44 51 53 25 10 10 10 31 13 33 46 54 57 58 59 70 Tab 84 Spare parts list for the hydraulic circuit Marker Reference Description 1 7699083 Flow meter 2 49834 G 3 8 air vent isolation valve 3 7606593 Automatic air vent 13 Spare parts 7654506 v06 19112019 123 ...

Страница 124: ...Dielectric elbow 28 7660282 Disconnector 29 300003520 HO VCZMQ6000E valve body 30 300003144 HO VC4013ZZ0 reversing valve motor 31 7729850 M3 4 M1 thermostatic mixing valve 32 7722069 3 kW electrical back up 33 7696821 PARA DN 15 8 pump 34 7101096 17 86 x 2 62 O ring 35 122097 Ø14 clip 36 96350203 Ø25 quick connection clip 37 300023113 Pin for DN20 38 7696905 Thermostatic valve domestic hot water p...

Страница 125: ...0V 85554908 7717537 3 Way Valve DHW ON OFF Electrical back up 7726152 7740282 7717840 7699154 7699154 X12 X2 X11 X3 X4 X1 X6 X7 SENSOR TARGET SENSOR LIQUID FUSE X5 HPC 01 SCB 04 X6 X8 X9 X1 X2 X3 FUSE 7714999 7724253 7715217 7622563 BLUETOOTH 7715087 PUMP A H M I 7682206 R BUS Room Unit BL1 Multifunction BL2 Multifunction So So Energy counter Tout Outside temperature sensor Tdhw Domestic Hot Water...

Страница 126: ...Earth cable 14 7717873 Cable harness for three way valve internal power supply 15 7724256 L 950 pump cable 16 7724254 NTC 10K second circuit sensor 17 7658838 MK2 HMI display 18 7726152 Earth connection wire EHC PCB terminal block 19 7740282 Earth connection wire terminal block tank 20 7724255 Pump power supply cable 21 7717996 Power supply cable harness 13 2 Outside unit 13 2 1 AWHP 4 5 MR Fig 14...

Страница 127: ...lve coil LEV 18 7652680 Solenoid valve coil 21S4 19 7652681 4 way valve 20 7652682 Stop valve access panel 21 7652684 Electrical supply access panel 22 7652685 Sensor support 23 7652686 Outside temperature sensor RT65 24 7652687 Battery temperature sensor RT68 25 7652688 Sensor kit RT61 RT62 26 7652690 Fuse holder 27 7652691 Fuse T20AL 250 V 28 7652692 Supply terminal 29 7652693 Central unit PCB 3...

Страница 128: ...erence Description 1 7673303 Fan grate 2 7673305 Front panel 3 7673306 Base panel 4 7673313 Cable duct 5 7673307 Maintenance access panel 6 7673308 Hatch 7 7673309 Rear protection grid 8 7673310 Side panel right 9 7673311 Motor bracket 10 7673312 Top panel 13 Spare parts 128 7654506 v06 19112019 ...

Страница 129: ...4 1 Marker Reference Description 1 7673314 Fan motor 2 7673315 Fan rotor 3 7604150 Nut 4 7673316 Self ACL 5 7673317 TH4 TH34 temperature sensor 6 7673318 SNB130FTCM2 compressor 7 7673319 Power receiver 8 7673320 CPLT 1 4 F 1 2 F stop valves 9 7673321 LEV B coil 10 7673322 LEV A coil 13 Spare parts 7654506 v06 19112019 129 ...

Страница 130: ...4 way valve coil 19 7673329 HP pressure switch sensor 20 300018123 41 5 bar HP pressure switch 21 300023673 Connection terminal block 23 7673330 Cover 24 7673331 Support 25 7673332 Central unit PCB 26 7673333 Relay card 27 7673334 Radiator support 28 7673335 TH8 radiator sensor 29 7673336 Compressor top insulation 30 7673337 Compressor insulation 0 7673338 10 A 250 V fuse 0 7673339 3 15 A 250 V fu...

Страница 131: ... REF AWHP 8 MR 2 R2 UK 5 7614223 Motor bracket SERVICE REF AWHP 8 MR 2 5 7705553 Motor bracket SERVICE REF AWHP 8 MR 2 R2 UK 6 7614224 Valve bracket 7 7614225 Grip 8 7614226 Lower front panel 9 7614227 Lower rear panel 10 7614228 Side panel right SERVICE REF AWHP 8 MR 2 10 7705557 Side panel right SERVICE REF AWHP 8 MR 2 R2 UK 11 7614230 Maintenance access panel 12 7614231 Rear protection grate 13...

Страница 132: ... pressure pressure switch 6 7614240 Compressor TNB220FLHMT SERVICE REF AWHP 8 MR 2 6 7652256 Compressor SNB220FAGMC L1 SERVICE REF AWHP 8 MR 2 R1 UK SERVICE REF AWHP 8 MR 2 R2 UK 7 7614241 TH34 compressor discharge temperature sensor 8 7614242 Anti vibration stud SERVICE REF AWHP 8 MR 2 8 7705559 Anti vibration stud SERVICE REF AWHP 8 MR 2 R2 UK 9 7614243 Load plug 10 7614244 Stop valve 3 8 11 761...

Страница 133: ... 22 7614279 Control panel 23 7614280 Self DCL SERVICE REF AWHP 8 MR 2 23 7705563 Self 18 MH SERVICE REF AWHP 8 MR 2 R2 UK 24 7614282 EMI suppressor filter 25 7614283 Dissipator sensor TH8 SERVICE REF AWHP 8 MR 2 25 7705564 Dissipator sensor TH8 SERVICE REF AWHP 8 MR 2 R2 UK 26 7614284 Output PCB SERVICE REF AWHP 8 MR 2 26 7652259 Output PCB SERVICE REF AWHP 8 MR 2 R1 UK SERVICE REF AWHP 8 MR 2 R2 ...

Страница 134: ...te condi tions 133 00 130 00 123 00 Sound power level LWA indoors 2 dB 30 35 34 Ability to off peak hours functioning 2 No No No Rated heat output under colder warmer climate conditions kW 5 4 4 4 6 6 Space heating Annual energy consumption under colder warmer climate conditions kWh GJ 1 4483 1173 3721 1394 4621 2029 Water heating Annual energy consumption under colder warmer climate conditions kW...

Страница 135: ...ating energy efficiency of package under average climate Auxiliary electricity Solar contribution Water heating energy efficiency of combination heater from fiche of solar device Colder Warmer Water heating energy efficiency under colder and warmer climate conditions Declared load profile I The value of the water heating energy efficiency of the combination heater expressed in II The value of the ...

Страница 136: ...uilding size and characteristics Seasonal space heating energy efficiency class of package under average climate Seasonal space heating energy efficiency of package under average climate Tank rating Collector efficiency in Tank volume in m Collector size in m Seasonal space heating energy efficiency in Supplementary boiler Class I 1 Class II 2 Class III 1 5 Class IV 2 Class V 3 Class VI 4 Class VI...

Страница 137: ...rature heat pumps Prated Prated Psup 1 2 II package without hot water storage tank II package with hot water storage tank 0 1 00 1 00 0 1 0 70 0 63 0 2 0 45 0 30 0 3 0 25 0 15 0 4 0 15 0 06 0 5 0 05 0 02 0 6 0 02 0 0 7 0 0 1 The intermediate values are calculated by linear interpolation between the two adjacent values 2 Prated is related to the preferential space heater or combination heater Tab 8...

Страница 138: ...14 Appendix 138 7654506 v06 19112019 ...

Страница 139: ...chnological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent in writing Subject to alterations ...

Страница 140: ...7654506 v06 19112019 7654506 001 06 ...

Отзывы: