Tab.41
Parameter
Description
Factory setting
DP051
ECO mode: use of the heat pump only. Comfort mode: use of the heat pump and
backup energy sources
0 = ECO (Only HP)
1 = Comfort (HP+Boiler)
0
DP120
Hysteresis temperature relative to the DHW temperature setpoint
Can be set from 0 °C to 40 °C
8
DP213
Post run time of the DHW pump/3 way valve after DHW production
Can be set from 0 Min to 99 Min
3
ADV
ADV advanced parameters
7.2.4
Installer \DHW\ADV menu
A domestic hot water sensor must be connected to the EHC–06 PCB to
display these parameters.
DP : Direct Hot Water Parameters = Domestic hot water tank parameters
Tab.42 List of ADV parameters in the sub-menu of the Installer menu
ADV
Description of the ADV advanced parameters
Factory setting
DP004
Legionella mode protection calorifier
0 =Disabled
1 = on: the domestic hot water tank is superheated to 65 °C for 20 minutes
once a week.
2 = automatic: the domestic hot water tank is remotely controlled.
0
DP046
Maximum domestic hot water temperature
Can be set from 10 °C to 70 °C
70
DP047
Maximum duration of the domestic hot water production
Can be set from 1 to 10 hours
3 (4.5 kW - 6 kW - 8
kW)
2 (11 kW - 16 kW)
DP048
Minimum heating duration between two periods of domestic hot water production
Can be set from 0 to 10 hours
2
DP055
Enable/disable the TAS protection of the DHW tankCan be set from 0 to 1
0
DP090
Delay time for starting the backup energy source for DHW
Can be set from 0 Min to 120 Min
90
DP160
Setpoint for DHW anti legionella
Can be set from 60 °C to 90 °C
Do not modify this setting
65
7.2.5
Installer \EHC–06 and SCB-04 menu
AP : Appliance Parameters = Appliance parameters
7 Settings
68
7654506 - v06 - 19112019
Содержание MIC V200
Страница 138: ...14 Appendix 138 7654506 v06 19112019 ...
Страница 140: ...7654506 v06 19112019 7654506 001 06 ...