5.3.1
Data plate on the indoor module
The data plate of the indoor module is located on the top of the appliance.
A second data plate is affixed to the inside of the front panel.
5.3.2
Data plate on the outdoor unit
5.4
Respecting the distance between the indoor module and the outdoor unit
To ensure that the heat pump functions correctly, respect the minimum
and maximum connection lengths between the indoor module and the
outdoor unit.
1. Respect distances A, B and C between the outdoor unit 1 and the
indoor module 2.
Tab.19
A: Maximum/
minimum length
B: Maximum
height differ
ence
C: Maximum
number of el
bows
AWHP 4.5 MR 2 to 30 m
30 m
10
AWHP 6 MR-3 2 to 40 m
30 m
15
AWHP 8 MR-2 2 to 40 m
30 m
15
2. Make one or two horizontal loops with the refrigerant connections to
reduce disruption.
If the length of the refrigerant connections is less than 2 m, disruptions
can occur:
Functional disruptions caused by a fluid overload,
Noise pollution caused by the circulation of the refrigerant.
5.5
Positioning the indoor module
5.5.1
Choosing the location for the heat pump
Caution
The indoor module must be installed in a frost-free location.
1. Decide on the ideal location, bearing in mind the space required by
the heat pump and any legal directives.
Fig.34
MW
-30
0
06
8
7-
3
Fig.35
MW-6000694-1
Fig.36
MW-M001439-2
A
B
2
1
C
5 Installation
34
7654506 - v06 - 19112019