Accessories and Spare Parts
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
295
11
11.3.4 Electrical data mains filter
TN/TT systems
BFN 3-1-... -001
0007
0016
0030
0042
0056
0075
0100
0130
0180
Max. input supply voltage
3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
=
50 °C)
7 A
16 A
30 A
42 A
56 A
75 A
100 A
130 A
180 A
Peak current
(at T
B
= 50 °C)
1.5 x I
N
for < 1 min per hour
Current derating
Test voltage
line - line: 2125 V
DC
/ 2 s
line - housing: 2125 V
DC
/ 2 s
Connection
L1/L2/L3: safe-to-touch screw terminals
PE connection: bolt M5 / M6 / M10
Maximum connection
cross-section
4
mm
2
4
mm
2
10
mm
2
10
mm
2
16
mm
2
25
mm
2
50
mm
2
50
mm
2
50
mm
2
Power loss (typical)
4 W
8 W
12 W
15 W
18 W
24 W
24 W
30 W
35 W
Protection class
IP 20
EPCOS
B84143A0150R410
Max. input supply voltage
3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
=
50 °C)
150 A
Peak current
(at T
B
= 50 °C)
1.5 x I
N
for < 1 min per hour
2.5 x I
N
for < 1 min per hour
Test voltage
line - line: 2240 V
DC
/ 2 s
line - housing: 2720 V
DC
/ 2 s
Connection
L1/L2/L3: safe-to-touch screw terminals
PE: bolt M10
Maximum connection
cross-section
95 mm
2
Protection class
IP 20
I
I
rated
85
ambient
35°C
--------------------
–
=
Содержание b maxx BM4400
Страница 137: ...Design and Operation Instruction handbook b maXX BM4400 BM4600 BM4700 Document No 5 12008 07 137 of 358 4 ...
Страница 322: ...Instruction handbook b maXX BM4400 BM4600 BM4700 Document No 5 12008 07 Baumüller Nürnberg GmbH 322 of 358 A ...
Страница 358: ...Instruction handbook b maXX BM4400 BM4600 BM4700 Document No 5 12008 07 Baumüller Nürnberg GmbH 358 of 358 Notes ...
Страница 359: ......