Electrical data basic units
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
Baumüller Nürnberg GmbH
74
3.4
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
Using the power choke listed in
on page 300 at a power supply with U
K,power supply
= 0.4 %.
3)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U
AC
3 0 V to
3
U
DC
2
-----------
10 V
–
=
without overmodulation of the PWM.
4)
Switching frequency of the inverter (adjustable).
5)
RMS at an environmental temperature of 40 °C.
6)
At rated power supply voltage the unit supplies rated / maximum output currents. With input voltages above the rated power supply
voltage the output currents must be reduced at constant output power.
Ou
tput curren
t [%]
Derating of the output current BM4444
Power supply voltage [V]
Ou
tput curren
t [%]
Derating of the output current BM4444
Power supply voltage [V]
Output
cur
rent [%
]
Derating of the output current BM4445
Power supply voltage [V]
Output
cur
rent [%
]
Derating of the output current BM4446
Power supply voltage [V]
Figure 36:
Derating the output current BM444X universal units
7)
The input current must be reduced between 40 °C and 55 °C. See correction factors at changed operating conditions
8)
The peak output current is supplied for the maximum peak current period for the motor at the first acceleration (cold power unit). The in
fact possible overload time is dependent on the preload of the device and on the heat sink temperature, it is determined by the overload
monitoring of the device.
9)
Peak current can be supplied at a heat sink temperature of <75 °C (BM4X43) and <80 °C (BM4X44), only.
If these heat sink temperature thresholds are exceeded, the output current is automatically derated to the rated current.
10)
For cooling versions S and A, only.
11)
The sum of the transmitted mean effective power via the DC link terminals and the mean effective power at the motor terminals, may
not exceed the specified value continuously.
12)
Available at device with type code BM44XX-XX-XXXXX-03 with controller version code 4-yyy-xxx, whereat yyy > 024
and
the controller
firmware version must be 3.09 or higher. Switching off a device at a motor short circuit may damage the device.