Safe Torque Off (STO)
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
Baumüller Nürnberg GmbH
336
C.2
Figure 112:
Timing diagram: Recommended starting / shutdown sequence.
Different starting / shutdown sequences possible. See table
Different starting / shutdown op-
1
T
Boot_controller
dependent on the used option module (from firmware version 03.05)
approx. 5 s.
2
T
charge DC link
: 1.5 s
(exception BM4X3X: 6 s).
3
T
SR pulse enable
: 20 ms
(exception BM4X2X: 200 ms).