Operation
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
207
8
m
Power supply ON after 24 V ON
Power supply
X200 Supply 24 V
X1:6 Ready-to-operate
X300:1 Signal bus
300 ms
X300:2 Signal bus phase failure
ready-to-operate
3 s
Using a BM5030:
T ~ 6 50
C
int
C
ext
+
1s
+
Figure 93:
Timing diagram power supply ON after 24 V ON
m
24 V ON before power supply ON signal bus
Power supply
X200 Power supply 24 V
X1:6 Ready-to-operate
X300:1 Signal bus ready-to-operate
5,4 s
Using a BM5030:
2,4 s < T < 6 50
C
int
C
ext
+
1s
+
Figure 94:
Timing diagram 24 V ON before Power supply ON signal bus