Operation
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
209
8
m
Long power failure (> 10 s)
Power supply
X1:5 Error
t > 10 s
Using a BM50XX-XXX
0
10 s
240 ms
X1:4 Reset
As soon as X1:5 is in error state the reset signal can be given, it is also possible
to give the reset signal after the power supply is available again.
X300:2 Phase failure
One period
300 ms
of power supply
Depending on
150 ms
1.2 s to 3.2 s
Usning a BM5030:
1.2 s < T < 6 50
C
int
C
ext
+
1s
+
the loading state
of the DC link
1)
X1:6 Ready-to-operate
X300:1 Signal bus ready-to-operate
Figure 97:
Timing diagram long power failure (> 10 s) BM50XX-XXX0
1)
The length of the time period until the Ready-to-operate signal is available again depends on the loading
state of the DC link. The higher the DC link voltage has been, the shorter the time period until the returning
of the Ready-to-operate signal will be.
Содержание b maXX 5000
Страница 101: ...Design and Operation Instruction handbook b maXX 5000 Document No 5 09021 16 101 of 328 4 ...
Страница 220: ...Fieldbus communication Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 220 of 328 8 4 ...
Страница 240: ...Error handling Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 240 of 328 10 4 ...
Страница 298: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 298 of 328 A ...
Страница 299: ...299 of 328 Operation Manual b maXX 5000 Document no 5 09021 16 APPENDIX B DECLARATION OF CONFORMITY ...
Страница 324: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 324 of 328 Table of Figures ...
Страница 328: ...Instruction handbook b maXX 5000 Document No 5 09021 16 Baumüller Nürnberg GmbH 328 of 328 Notes ...
Страница 329: ......