Manual 2100-642
Page
76 of 82
Screen
Menu Item
Range
Default Value
Current I/O Value
Delay Up
0-999 sec
105
Information only
Delay Down
0-999 sec
60
Setpoint
77
CONTROL DEADBAND:
ZONE 2 HEAT
Direction
Direct/Reverse
Reverse
Stages
0-99
1
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Delay Up
0-999 sec
60
Delay Down
0-999 sec
60
Setpoint
60
CONTROL DEADBAND:
ZONE 3 COOL
Direction
Direct/Reverse
Direct
Stages
0-99
2
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Delay Up
0-999 sec
60
Delay Down
0-999 sec
60
Setpoint
77
CONTROL DEADBAND:
ZONE 3 HEAT
Direction
Direct/Reverse
Reverse
Stages
0-99
2
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Delay Up
0-999 sec
60
Delay Down
0-999 sec
60
Setpoint
60
STAGE
DIFFERENTIALS
CL1/On
0-99
1
CL1/Off
0-99
-1
CL2/On
0-99
3
CL2/Off
0-99
1
CL3/On
0-99
4
CL3/Off
0-99
2
HT1/On
0-99
1
HT1/Off
0-99
-1
HT2/On
0-99
3
HT2/Off
0-99
1
APPENDIX: LC-SERIES CONTROLLER AND TEC-EYE ARCHITECTURE (CONT.)
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...