Manual 2100-642
Page
75 of 82
Screen
Menu Item
Range
Default Value
Current I/O Value
8
FACTORY
MANUFACTURER
Configuration
CONFIGURATION
Temperature Units
F/C
F
Pressure units
PSI/BAR
PSI
Force Clock Enable
Yes/No
Yes
Clock Mode
12/24
24
Disable Buzzer
Yes/No
Yes
Startup Delay
0-9999 sec
30 sec
DAMPER ALARM
DELAYS
Detect Open
0-999 sec
20
Detect Close
0-999 sec
300
DAMPER DAILY TEST
Enable
Yes/No
Yes
Duration
0-999 sec
30
Voltage
0-10 V
2.5
CONTROL DEADBAND:
ZONE 1 COOL
Direction
Direct/Reverse
Direct
Stages
0-99
4
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Delay Up
0-999 sec
120
Delay Down
0-999 sec
60
Setpoint
77
CONTROL DEADBAND:
ZONE 1 HEAT
Direction
Direct/Reverse
Reverse
Stages
0-99
4
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Delay Up
0-999 sec
111
Information only
Delay Down
0-999 sec
60
Setpoint
60
CONTROL DEADBAND:
ZONE 2 COOL
Direction
Direct/Reverse
Direct
Stages
0-99
1
Up Differential
-99.9 to 99.9
2
Down Differential
-99.9 to 99.9
-2
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...