Manual 2100-642
Page
39 of 82
3. If after 2 minutes, the low pressure switch is
still open, or opens again immediately aftward,
the board will delay for 2 minutes again (soft
lockout).
4.
On the 3rd attempt, the board will lock out the
compressor and outdoor fan until manually reset.
• High Temperature 2 Alarm – Should the shelter
controller see 90°F, both free-cooling dampers will
open (regardless of outdoor temperature) to cool
the building.
• Smoke Alarm – Should the smoke detector send
an alarm signal to the controller, all blower,
compressor and ventilations functions cease.
• Freezestat – If coil temperature below 30°F is
sensed by the freezestat, the compressor will
deactivate for 5 minutes, or until the sensor sees
55°F, whichever comes first.
FIGURE 2.2
Wall-Mount Unit Control Board
Dirty Filter Switch
High Pressure Alarm Relay
Low Pressure Switch
Air Proving Switch
Damper Blade Switch
2-10VDC Free-Cooling Damper Signal
Common
Common/Control Ground
24VAC from Transformer
24VAC Output to Motor Start Relay
+24VAC Power Input
24V to OA Humidity Sensor
Ground
Outdoor Air Humidity Sensor 4-20mA
Return Air Temp Sensor 10kΩ
Outdoor Air Temp Sensor 10kΩ
Mixed Air Temp Sensor 10kΩ
–24VAC from Transformer
+24VAC from Transformer
Freezestat Sensor 10kΩ
– Communication Wire
+ Communication Wire
24VAC Cooling Output to Compressor Control Module
24VAC Heating Stg2 Output to Limit Switch
24VAC Heating Stg1 Output to Limit Switch
+24VAC Power Input
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...