PROBE ADJUSTMENT
Indoor Temp
Indoor Temp
Offset
-9.9 to +9.9
CONTROL SETTINGS
Displays unit information
Service Settings
ZONE 1
Average/Highest
Average
ZONE 2
Average/Highest
Average
ZONE 3
Average/Highest
Average
HUMIDIFIERS
None
None
Z1-1
Z1-2
Z1-3
Z1&Z2
Z1&Z2&Z3
Modulating Setup:
Humidifier Zone 1
Setpoint
1-999
45
Band
1-999
20
Modulating Setup:
Humidifier Zone 2
Setpoint
1-999
45
Band
1-999
20
Modulating Setup:
Humidifier Zone 3
Setpoint
1-999
45
Band
1-999
20
Setpoint
FREECOOL
Enthalpy/Dry
Bulb/None
Enthalpy
MIXED AIR SETPOINT
1-99
55
FREECOOL OAT
1-99
40
DIFFERENTIAL
1-99
5
RAT-OAT DIFF
1-99
10
HUMIDITY SETPOINT
30-70
45
DEHUM DIFF
1-9.9
5
Setpoint: Mixed Air Alarm
HIGH DIFFERENTIAL
28-65 deg
5
LOW DIFFERENTIAL
1-99 deg
5
ALARM DELAY
0-999 sec
10 sec
Setpoint: Zone Temp Alarm
Z1 High Alarm
70-120 deg
85
Z1 High Alarm 2
70-120 deg
90