Manual 2100-642
Page
47 of 82
Description
Range
Default Setpoint
Units
Temperature at local remote
(main) sensor
--
--
--
Temperature Setpoint
65 - 90
77
°F
Heating Setpoint
52 -75
60
°F
Temperature High Limit -
Level 1
70 - 120
85
°F
Temperature High Limit -
Level 2
70 - 120
90
°F
Temperature Low Limit
28 - 65
45
°F
Cooling Stage Differential
1 - 5
5
°F
Heating Stage Differential
1 - 5
2
°F
Comfort Mode Setpoint
65 - 80
72
°F
Comfort Mode Operation Time
30 - 90
60
Minutes
Freecooling Setpoint
--
55
°F
Lead-Lag Changeover Time
(Rotation)
1 - 30 days, or 0 for disabled
1
Day(s)
Temperature Units
°F/°C
°F
--
TABLE 2.3
Controller Programmable Features and Default Settings
The Bard 575 volt wall mount unit system has been pre-programmed with what is widely
considered to be the best settings for efficiency and operation. Any changes to internal
programming through the LC-Series Controller or the TEC-EYE not covered within this manual
may cause the systems to operate improperly, cause internal damage to the HVAC units, cause
the shelter to overheat, or other very serious consequences. Although complete controller
programming architecture for both the LC-Controller and TEC-EYE has been provided, going
outside the boundaries of what has been covered in this manual is not recommended.
CAUTION
4. Go to Analog Inputs, press ENTER key.
5. To enable Zone 2 and Zone 3 temperature sensors,
move cursor to desired zone by pressing the
ENTER key:
Zone 2: Go to Remote Zone 2. Press ENTER key to
change EN: OFF to ON, Ch: BOO3.
Zone 3: Go to Remote Zone 3. Press ENTER key to
change EN: OFF to ON, Ch: B004.
6. To enable Zone 2 and Zone 3 humidity sensors,
move cursor to desired zone by pressing the
ENTER key:
Zone 2: Go to Humidity Zone 2. Press ENTER key
to change EN: OFF to ON, Ch: BOO7.
Zone 3: Go to Humidity Zone 3. Press ENTER key
to change EN: OFF to ON, Ch: B005.
Acknowledging/Clearing Alarms
Alarm conditions activate a red LED indicator that
backlights the ALARM function key. As an option, an
alarm condition may also be enunciated by an audible
alarm signal. An alarm is acknowledged by pressing the
ALARM key. This calls up alarm display screen(s) that
provide a text message detailing the alarm condition(s).
After an alarm condition is corrected, the alarm can be
cleared by pressing the ALARM key.
Simulating Smoke Alarm
1. Go to Technician menu, press ENTER key.
2. Go to Manual Management, press ENTER key.
3. Go to Digital Inputs, press ENTER key.
4. Press the ENTER key to move the cursor to Smoke
Manual DI 1 and press ENTER key.
5. Press UP or DOWN arrow keys to change the value
from "Open" to "Closed"; alarm activates.
6. Reverse procedure to terminate test.
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...