Compressor
1. Go to Technician menu, press ENTER key.
2. Go to Manual Management, press ENTER key.
3. Go to Relay Output, press ENTER key.
4. Go to Relay Output Cooling Stage. Press UP or
DOWN arrow keys to change Manual Relay to
“ON”; press ENTER key. Press UP or DOWN arrow
keys to change manual position to “ON” and press
ENTER key.
5. Verify compressor is running.
Heat
1. Go to Technician menu, press ENTER key.
2. Go to Manual Management, press ENTER key.
3. Go to Relay Output, press ENTER key.
4. Go to Relay Output Heating, press ENTER key.
5. Press UP or DOWN arrow keys to change Manual
Relay and Manual Position to “ON” and press
ENTER key.
6. Verify heater “ON” status.
7. Repeat Steps 1-6 to enable Stage 2 heat. (Before
enabling Stage 2 heater, make sure the Stage 2
heater option is enabled under Unit Set-Up.)
The Bard 575 volt wall mount unit system has been pre-programmed with what is widely
considered to be the best settings for efficiency and operation. Any changes to internal
programming through the LC-Series Controller or the TEC-EYE not covered within this manual
may cause the systems to operate improperly, cause internal damage to the HVAC units, cause
the shelter to overheat, or other very serious consequences. Although complete controller
programming architecture for both the LC-Controller and TEC-EYE has been provided, going
outside the boundaries of what has been covered in this manual is not recommended.
CAUTION
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...