Manual 2100-642
Page
69 of 82
Screen
Menu Item
Range
Default Value
Description
OHM x 5
Min
-3276.8 to
3276.7
0
Max
-3276.8 to
3276.8
100
Offset
-99.9 to 99.9
nu13
Min
-3276.8 to
3276.7
Max
-3276.8 to
3276.8
Offset
-99.9 to 99.9
nu12
Min
-3276.8 to
3276.7
Max
-3276.8 to
3276.8
Offset
-99.9 to 99.9
SPKP0087TO
Offset
-99.9 to 99.9
nu10
Min
-3276.8 to
3276.7
Max
-3276.8 to
3276.8
Offset
-99.9 to 99.9
10T170
Offset
-99.9 to 99.9
-50T90
Offset
-99.9 to 99.9
NTCHT
Offset
-99.9 to 99.9
0-5VDC
Min
-9999.9 to
9999.9
Max
-9999.9 to
9999.9
Offset
-99.9 to 99.9
Current Value
Out of Range Alarm
Will show if input out of range
Power Delay
0-999 seconds
5 seconds
Power up delay
Run Delay
0-999 seconds
5 seconds
Units
Temp /Other/
Pressure
Temp