Information (cont.)
POWER CYCLE STATUS
Last Off Time
Time/Date
Last time controller powered off
Last On Time
Time/Date
Last time controller powered on
Length of Last Off Time
Hours/Minutes
Length of last off time
UNIT SETUP
Setpoint
Total Units
1-24
1
Total units connected
Pressure Sensor
On/Off
Off
Room pressure sensor enabled
Configuration
Temperature Units
F/C
F
Pressure Units
PSI/BAR
PSI
WORKING HOURS
Run Hours
COMPRESSOR
STAGE 1
Run Hours
000H
Displays number of run hours
Number Starts
00000
Displays number of unit starts
COMPRESSOR
STAGE 2
Run Hours
000H
Displays number of run hours
Number Starts
00000
Displays number of unit starts
FREE COOL
Run Hours
000H
Displays number of run hours
Number Starts
00000
Displays number of unit starts
HEAT STAGE 1
Run Hours
000H
Displays number of run hours
Number Starts
00000
Displays number of unit starts
HEAT STAGE 2
Run Hours
000H
Displays number of run hours
Number Starts
00000
Displays number of unit starts
BMS CONFIGURATION
BMS Port 1
PROTOCOL
LON
Modbus EXT
Communications protocol
BACNET IP/ETH
BACNET MSTP
MODBUS EXT
PCOLOAD
MODBUS
MODEM
CAREL
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...