Manual 2100-642
Page
61 of 82
Signal
Description
Possible Cause
Component to Check
Recommended Action
Device
Actions
Free Cooling
Damper Fails to
Close Alarm
Alarm is reset
automatically.
DC free cooling damper
fails to close.
Check the damper
linkage. Check to see
if anything is in the
way of the damper.
Indoor Blower:
On
Damper: Off
Communication
Failed Alarm
Alarm is reset
automatically.
Communication is lost
with the LC1000-100
main controller.
Check the RS485
port. Check for
damage to the
communications
cable between the
PLC controllers.
Reconnect the
communications
cable. If the PLC
controller board
RS485 port is
defective, replace.
Mixed Air
Temperature
Sensor Failed
Alarm
(B001)
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
Check the mixed air
temperature sensor
wiring.
Check temperature
vs. resistance of
temperature sensor
(see Table 2.5 on
page 52).
Replace the supply
air temperature
sensor.
Outdoor
Temperature
Sensor Failed
Alarm
(B002)
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
Check the outdoor
temperature sensor
wiring.
Check temperature
vs. resistance of
temperature sensor
(see Table 2.5 on
page 52).
Replace the outdoor
temperature sensor.
Outdoor
Humidity Sensor
Failed Alarm
(B005)
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
Check the humidity
sensor wiring.
Replace the humidity
sensor.
Return Air
Temperature
Sensor Failed
Alarm
(B003)
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
The alarm is activated
if the sensor is faulty, a
sensor wire is loose or
an out-of-range value
is read.
Check the return air
temperature sensor
wiring.
Check temperature
vs. resistance of
temperature sensor
(see Table 2.5 on
page 52).
Replace the return air
temperature sensor.
NEED ASSISTANCE?
This document contains the most current product information as of this printing. For
the most up-to-date product information, go to
www.bardhvac.com
where there are links
to product specifications, installation instructions, replacement parts manuals, and
wiring diagrams. Should any assistance be required during the installation or servicing
of this product, contact the Bard Technical Service Department at 419.636.0439.
TROUBLESHOOTING TEC-EYE ALARMS (CONT.)
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...