Manual 2100-642
Page
34 of 82
FIGURE 1.28
Executing Run Test
Description
Default Setpoint
Temperature at local remote
(main) sensor
--
Temperature Setpoint
77°F
Heating Setpoint
60°F
Temperature High Limit –
Level 1
85°F
Temperature High Limit –
Level 2 (High Temp Alarm)
90°F
Temperature Low Limit
45°F
Cooling Stage Differential
1°F
Minimum Compressor Run
Time
3 Minutes
Minimum Compressor Off
Time
2 Minutes
Comfort Mode Setpoint
72°F
Comfort Mode Operation
Time
60 Minutes
DC Freecooling Setpoint
55°F
Lead/Lag Changeover Time
(Rotation)
1
Temperature Units
°F
TABLE 1.3
Controller Default Settings
Run Test Approximate Timings (in Minutes)
Blower
On: 0:00
Damper
Open: 0:00 – 2:40
Closed: 2:41 – 4:57
Compressor On: 4:58
Off: 6:00
Heat
On: 6:01
Off: 7:10
Blower
Off: 8:19
6. Complete Installation
Once all the installation steps have been completed,
and system verification and run test results were
satisfactory, the installation can now be considered
“complete.” The Bard-Link
TM
PLC lead/lag controller
has been pre-programmed with what is widely
considered to be the most efficient operating
parameters—see Table 1.3. Further information
on exact sequence of operation and advanced
programming changes can be found in the Service
Instructions section of this manual.
WEB CARD COMMUNICATION BOARD
NOTE:
A web card communications board allows
remote access, via Ethernet, to all functions of the
controller system. This is the same as if one was in
the building where the controller system is physically
installed.
Connect the Bard-Link
TM
LC5000-100 controller
Ethernet port to the existing Ethernet card in the
shelter (if applicable) using CAT 6 Ethernet cable.
5) Press ENTER key to scroll to Enable. Press UP
or DOWN arrow keys to change No to Yes. Unit
will begin the run test (see Figure 1.28).
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...