Manual 2100-642
Page
33 of 82
FIGURE 1.25
Status Display Showing Units "Online"
4. Verify Communication to Units
Check controller display to see that all units are "online".
This typically takes 3-4 minutes after controller is
powered. If all units are online, the display will appear
as shown in Figure 1.25. If any of the units are not
online, the display will appear as shown in Figure 1.26.
To determine which unit or units are offline:
1) Press MENU button to go to main menu.
2) Go to Board Switch menu, press ENTER.
Display will show which unit or units are
offline (see Figure 1.27). Units offline will
show up as "no device connected". In Figure
1.27, Unit 3 is not showing up as online.
3) Check the wiring connections on the units
showing as offline.
4) Repeat Steps 1-3 to confirm unit online status
and further diagnose connection issues if
necessary.
5. Run Test Units
Using the TEC-EYE, a run test should be executed
on each unit to verify the equipment is functioning
correctly.
1) On the TEC-EYE, go to Technician menu,
press ENTER key.
2) Press UP or DOWN arrow keys to get to
Service Settings menu, press ENTER key.
3) Press UP or DOWN arrow keys to get to Control
Setting menu, press ENTER key.
4) Cursor will be flashing in upper left corner
of screen. Press DOWN arrow key to scroll
through screens to Run Test.
Board Switch Display Icons
FIGURE 1.26
Status Display Showing Units "Offline"
FIGURE 1.27
Board Switch Display
Unit 3 not showing
as online
LC5000-100 and
TEC-EYE Displays
LC5000-100
Controllers (I/O Boards) active in network
Display(s) active in network
No device connected
Units
Содержание W48A2PQ
Страница 6: ...Manual 2100 642 Page 6 of 82...
Страница 7: ...Manual 2100 642 Page 7 of 82 SECTION 1 INSTALLATION INSTRUCTIONS...
Страница 35: ...Manual 2100 642 Page 35 of 82 SECTION 2 SERVICE INSTRUCTIONS...
Страница 62: ...Manual 2100 642 Page 62 of 82...
Страница 63: ...Manual 2100 642 Page 63 of 82 SECTION 3 APPENDIX...