Manual 2100-419E
Page
48 of 48
THE FOLLOWING INFORMATION IS NEEDED
TO CHECK PERFORMANCE OF UNIT
FLUID SIDE DATA
Cooling
** Heating
9. Entering fluid temperature
F
10. Leaving fluid temperature
F
11. Entering fluid pressure
PSIG
12. Leaving fluid pressure
PSIG
13. Pressure drop through coil
PSIG
14. Gallons per minute through the water coil
GPM
15. Liquid or discharge line pressure
PSIG
16. Suction
line
pressure
PSIG
17. Voltage at compressor (unit running)
V
18. Amperage draw at line side of contactor
A
19. Amperage at compressor common terminal
A
20. * Suction line temperature 6” from compressor
F
21. * Superheat at compressor
F
22. * Liquid line temperature at metering device
F
23. * Coil
subcooling
F
INDOOR SIDE DATA
Cooling
** Heating
24. Dry bulb temperature at air entering indoor coil
F
25. Wet bulb temperature of air entering indoor coil
F
26. Dry bulb temperature of air leaving indoor coil
F
27. Wet bulb temperature of air leaving indoor coil
F
28. * Supply air static pressure (packaged unit)
WC
29. * Return air static pressure (packaged unit)
WC
30. Other information about installation
** When performing a heating test insure that second stage heat is not activated.
* Items that are optional
Содержание QW242
Страница 6: ...Manual 2100 419E Page 6 of 48 FIGURE 1 UNIT DIMENSIONS ...
Страница 9: ...Manual 2100 419E Page 9 of 48 FIGURE 4 INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE MIS 1564 ...
Страница 21: ...Manual 2100 419E Page 21 of 48 FIGURE 15 REMOTE THERMOSTAT WIRING DIAGRAM X OPTION ...
Страница 22: ...Manual 2100 419E Page 22 of 48 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION 4102 021A ...
Страница 23: ...Manual 2100 419E Page 23 of 48 4102 022C FIGURE 17 REMOTE THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION ...
Страница 41: ...Manual 2100 419E Page 41 of 48 FIGURE 27 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 329 ...
Страница 42: ...Manual 2100 419E Page 42 of 48 FIGURE 28 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 328 ...