INSTALLATION INSTRUCTIONS
MOUNTING THE UNIT
When installing a QW unit near an interior wall on the
left side, a minimum of 8 inches is required; 12 inches is
preferred.
When installing a QW unit near an interior wall on the
right side, a minimum of 12 inches is required as
additional space is required to connect the drain.
This clearance is required to allow for the attachment of
the unit to the wall mounting brackets and the side trim
pieces to the wall.
This unit is to be secured to the wall when there is not a
vent sleeve used with the wall mounting brackets
provided.
(NOTE: Wall mounting brackets are only
shipped on units with no vent inside.)
The unit itself,
the supply duct, and the free blow plenum are suitable
for “0” clearance to combustible material.
NOTE: When a wall sleeve is to be used attach the
unit to the sleeve with bracket supplied with
the wall sleeve.
Following are the steps for mounting the QW units for
reference see Figure 12 on page 17.
1. Attach wall mounting bracket to the structure wall
with field supplied lag bolts. The fluid piping
connections are to be within the confines of this
bracket. See Figure 1 for cabinet openings and
location of fluid coil connection points.
2. Position the unit in front of the wall mounting
bracket.
3. Remove the locking screws from the wheels. Refer
to Figure 11.
4. Roll the unit up to the wall mounting bracket. The
unit must be level from side to side. If any
adjustments are necessary, shim up under the rollers
with sheets of steel or any substance that is not
affected by moisture.
5. Secure the unit to the wall bracket with provided #10
hex head sheet metal screws. There are prepunched
holes in the cabinet sides, and the bracket has slotted
holes to allow for some misalignment.
6. Position the bottom trim piece to the unit and attach
with provided screws (dark colored).
7. Position side trim pieces to the wall and attach with
field supplied screws. There are two long and two
short pieces supplied. The long pieces are to enclose
the gap behind the unit. The short pieces are to fill
the gap behind the cabinet extension or the free blow
plenum box. They may be cut to suit the ceiling
height or overlap the unit side trim. There is
sufficient length to trim up to a 10'2" ceiling.
FIGURE 11
REMOVING LOCKING SCREWS FROM
WHEELS
MIS-1523
REMOVE SCREWS
FROM WHEELS
BEFORE ROLLING
INTO PLACE
Содержание QW242
Страница 6: ...Manual 2100 419E Page 6 of 48 FIGURE 1 UNIT DIMENSIONS ...
Страница 9: ...Manual 2100 419E Page 9 of 48 FIGURE 4 INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE MIS 1564 ...
Страница 21: ...Manual 2100 419E Page 21 of 48 FIGURE 15 REMOTE THERMOSTAT WIRING DIAGRAM X OPTION ...
Страница 22: ...Manual 2100 419E Page 22 of 48 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION 4102 021A ...
Страница 23: ...Manual 2100 419E Page 23 of 48 4102 022C FIGURE 17 REMOTE THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION ...
Страница 41: ...Manual 2100 419E Page 41 of 48 FIGURE 27 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 329 ...
Страница 42: ...Manual 2100 419E Page 42 of 48 FIGURE 28 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 328 ...