Manual 2100-419E
Page
14 of 48
FIGURE 9
FRESH AIR DAMPER REMOVAL
COMMERCIAL ROOM VENTILATOR OPTION
Before stating the removal make sure the power has
been turned off. The hinged return air grille must be
opened. The commercial room ventilator (CRV) can be
seen after the panel has been removed. The CRV must
be removed to gain access to the mist eliminator.
1. The two mounting screws in the front of the CRV
must be removed.
2. The power connectors for the CRV (located on the
right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector and
pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening in
the back of the unit. The mist eliminator must be raised
up and the bottom can be pulled toward the front of the
unit and removed.
MOUNTING SCREW
MIS-1627