Manual 2100-419E
Page
13 of 48
The
rear drain
can be used with wall thickness of up to
10 inches where a water trap can be installed between
the unit and the interior wall. See Figure 8B. The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket. The drain can
be routed through the floor or through the wall. If the
drain is routed through the wall, the drain line must be
positioned such that it will not interfere with the sleeve
flange or the grille. See Figure 8C.
If the drain is to
be routed through an unconditioned space, it must
be protected from freezing.
FIGURE 8C
REAR DRAIN (TOP VIEW)
WALL
BRACKET
MIST ELIMINATOR SERVICE (Optional –
only used with one of the vent options)
A mist eliminator is supplied with the wall sleeve. The
mist eliminator is constructed of aluminum frame and
mesh. The mist eliminator is located in the top section
of the wall sleeve and can be removed from the inside of
the building without removing the unit from the wall.
This requires that the ventilation package must be
removed.
The steps necessary to remove each of the vent options
are listed following.
It is recommended that the mist eliminator be inspected
annually and serviced as required. The mist eliminator
can be inspected from the outside of the building by
looking through the outdoor grille. The mist eliminator
can be serviced from the outside. The outdoor grille
must be removed to do so.
WALL (MAXIMUM
10” FOR REAR
DRAIN)
DRAIN LINE
COUPLINGS NOT
SHOWN BUT
RECOMMENDED
FOR EASE OF
REMOVABILITY
FOR SERVICE
SLEEVE
WATER
TRAP
UNIT
MIS-977
The mist eliminator can be cleaned by washing
with soap and water. The excess water should
be shaken off the mist eliminator before it is
reinstalled.
BAROMETRIC FRESH AIR DAMPER
(Optional)
Before start to remove make sure the power has
been turned off. The hinged return air grille
panel must be opened. The fresh air damper
assembly can be seen on the back of the unit.
Refer to Figure 9.
1. The fresh air damper is attached to the back
of the unit with one screw on either side of
the assembly. Both of the screws must be
removed.
2. Once the mounting screws are removed, tilt
the assembly down and lift it out.
The mist eliminator can be seen through the
opening. The mist eliminator must be raised up
and the bottom can be pulled toward the front of
the unit.
Содержание QW242
Страница 6: ...Manual 2100 419E Page 6 of 48 FIGURE 1 UNIT DIMENSIONS ...
Страница 9: ...Manual 2100 419E Page 9 of 48 FIGURE 4 INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE MIS 1564 ...
Страница 21: ...Manual 2100 419E Page 21 of 48 FIGURE 15 REMOTE THERMOSTAT WIRING DIAGRAM X OPTION ...
Страница 22: ...Manual 2100 419E Page 22 of 48 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION 4102 021A ...
Страница 23: ...Manual 2100 419E Page 23 of 48 4102 022C FIGURE 17 REMOTE THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION ...
Страница 41: ...Manual 2100 419E Page 41 of 48 FIGURE 27 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 329 ...
Страница 42: ...Manual 2100 419E Page 42 of 48 FIGURE 28 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 328 ...