background image

INSTALLATION AND

SERVICING

ECOMOD AHP60

26 and 32 kW

Air/water monobloc heat pump 

When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance 

specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal.

For the very latest copy of literature for specification and maintenance practices visit our website www.idealcommercialboilers.com  

where you can download the relevant information in PDF format.

September 2022

UIN 00U07352250-A

Содержание ECOMOD AHP60 26 kW

Страница 1: ...rm to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cat...

Страница 2: ......

Страница 3: ...PRE REQUISITES BEFORE COMMISSIONING 44 4 1 Verification before switching on 44 4 2 Switching On 45 4 3 Commissioning 45 4 4 Adjustment of the heat pump hydraulic flow 45 4 5 Operating diagram 46 4 6...

Страница 4: ...heck list 65 8 END OF PRODUCT LIFE 71 Symbols used in this document INFORMATION This symbol draws attention to comments CAUTION Failure to comply with these instructions may cause damage to the instal...

Страница 5: ...nce with the prevailing regulations and code of practice in particular The legislation on the handling of refrigerants Current I E E BS7671 Wiring Regulations CAUTION This device must be maintained by...

Страница 6: ...the responsibility of the installer and personnel performing operations on this machine to perform a risk analysis prior to any installation and work on the machine The elements indicated below are no...

Страница 7: ...Effect Level workers long term systemic effects inhalation 7035 mg m3 PNEC Predicted No Effect Concentration Water fresh water 0 142 mg l Aquatic intermittent emissions 1 42 mg l sediments fresh water...

Страница 8: ...ed below must only be performed by specialised technicians or qualified personnel ensure that other types de refrigerant do not contaminate the R32 keep the gas bottle in a vertical position when load...

Страница 9: ...ulic and electrical circuits Hydraulic connections The connection must comply with good engineering practices according to the regulations in force Reminder Make the assembly seals according to good e...

Страница 10: ...accordance with the regulations in effect and in particular to current I E E BS7671 Wiring Regulations The electrical installation must be equipped with a differential protection This appliance is des...

Страница 11: ...01 07 2022 11 74 Example of recommended connection diagram non exhaustive TO THE EXPANSION SYSTEM COMMAND TO ELECT CABINET...

Страница 12: ...technician must receive the appropriate training and instruction for their tasks in safe conditions Operators should be familiar with personal protective equipment and accident prevention rules prescr...

Страница 13: ...see Refrigerant Material Safety Data Sheet You should know that refrigerants may not develop an odor For any intervention on the heat pump system Wear appropriate PPE especially gloves and goggles En...

Страница 14: ...14 74 00U07352250 A_ EN AHP60 26 32 kW Installation Use and Maintenance...

Страница 15: ...elation to the values communicated in chapter 2 4 1 2 3 Definitions Change to monobloc heat pump to be installed outdoors only for heating and or domestic hot water application air water The outdoor a...

Страница 16: ...nergy efficiency Water 35 C 55 C Class A A A A Compressor Type Twin Rotary DC Inverter Oil type FW65S or equivalent Number of compressors 1 1 Quantity of oil L 1 5 1 5 Refrigerating circuits 1 1 Refri...

Страница 17: ...2 Weight for shipping kg 250 265 Weight in service kg 240 255 The above performances are given for the following operating conditions as per the standard 14511 2018 1 Heating external air temperature...

Страница 18: ...E 813 2013 dry temperature humid temperature of the external air 7 C 6 C in out water temperature 47 55 C The tolerance on the value of the total acoustic power level is 2 dB A The value is determined...

Страница 19: ...the outside air 7 C 6 C water temperature inlet outlet 47 55 C The tolerance on the value of the total sound power level is of 2dB A Value is determined according to EN 12102 1 2017 used in conjuncti...

Страница 20: ...ure 1 Frame sizes in mm for both 26kW and 32kW Front view Right hand side view Rear view Top view IN OUT 1 M G IN OUT 1 1 4 M G E electricity supply input Dimensions and weight Models 26 kW 32 kW A Le...

Страница 21: ...by loosening the screws as indicated in figure 2 3 To access the user terminal unit remove panel B by loosening the screws as indicated in figure 2 4 Insert the cables into the grommets at the rear of...

Страница 22: ...n with low water flow rates there may be anomalies in how the appliance operates or in the most critical cases the safety mechanisms may intervene Both outdoors and indoors if not insulated heated the...

Страница 23: ...el as well as the disconnection and re engagement flow rates for the flow rate controller Water flow rate on the condenser The nominal water flow rate is determined for a temperature difference of 5 C...

Страница 24: ...and damage the unit 3 Make sure that the unit remains horizontal while it is being moved 4 Before moving the unit check that the devices are suitable for lifting and preserving the integrity of the u...

Страница 25: ...al waste in livestock farms or gas emissions from agricultural machinery A few elements to watch for are also shown in Table on page 27 Determining which corrosive elements are present in the environm...

Страница 26: ...appliance does not disturb neighbours or users noise level draughts caused low temperature of the air blown causing a risk of freezing plants in its path Exterior installation on a roof or in an open...

Страница 27: ...acturers Oxides Nitrogen oxides NOX x x x Sulphur oxides SxOy x x Carbon oxides x x Volatile gases or liquids Sulphurs x x x Hydrogen fluoride x x Ozone x x Nitrous oxide Methane x Volatile Organic Co...

Страница 28: ...reduce the risks it is advisable to study the vibration transmissions from the machine to the building as well as piping reverberation 3 3 2 1 Principle of reflection of the noise emitted Inner court...

Страница 29: ...0mm Model A1 mm A2 mm B1 mm B2 mm AHP60 26 kW 400 700 1500 400 AHP60 32 kW 400 700 1500 400 Figure 7 Minimum installation clearances around the outdoor unit CAUTION Do not clog or cover the ventilatio...

Страница 30: ...shelter or an alcove causes the unit s performances to drop To limit this drop an alcove must have 2 open opposite faces in the axis of the fan If for positioning reasons the open sides cannot follow...

Страница 31: ...e on the base of the hydronic kit on the battery side for the drainage of any condensation that may penetrate through the pipes of the hydraulic system As these pipes are well insulated the production...

Страница 32: ...The positions laid down for the installation of the vibration shock absorbers for each type of heat pump are presented in the image below Models Despatch weight kg In service weight kg A mm B mm Xa m...

Страница 33: ...regions where the water is hard the use of a water softener does not imply any change in our Guarantee provided that the softener is adjusted in line with trade standards The water hardness must be gr...

Страница 34: ...application Refer to the Ecomod Heat Pump Control manual unit control and the design study It is imperative to install adjustment valves not supplied refer to the diagram library In the case of a casc...

Страница 35: ...mount of fill water plus the amount of make up water added during the life of the unit should not be more than three times the water capacity of the heating system If this guideline is not followed co...

Страница 36: ...ny of these three above parameters deviates from the above recommendations refer to a water treatment specialist to correct the problem Setting up a plate exchanger If the recommendations listed above...

Страница 37: ...fitted on the loading reintegration line The water in the supply filling line must be filtered properly beforehand to remove all impurities and suspended particles Ensure that a removable screen filt...

Страница 38: ...n mode Screen in OFF mode The circulator is activated for 5 minutes then switches off You can exit the system drain cycle manually To deactivate drain mode PRG MODE ESC PRG PRG OFF PSS 195 PSS OFF SF...

Страница 39: ...ent cable ducts The flow rate controller item B on the above hydraulic diagram that is factory fitted must ALWAYS be connected in compliance with the indications shown on the electrical wiring diagram...

Страница 40: ...with the inverters we recommend fitting a type B differential circuit breaker as fitting a different type of circuit breaker could lead to unwanted tripping The following table shows the recommended c...

Страница 41: ...01 07 2022 41 74 AHP60 26 32 kW Installation Use and Maintenance...

Страница 42: ...aph 2 5 2 The terminal block must be connected in compliance with the remarks below L1 L2 L3 N PE General power supply F1 3 x fuse 32A 10 3 x 38 K1 phase controller Figure 13 Power terminal block 26 3...

Страница 43: ...red in the factory set H84 21 Inverter contact single phase voltage 230Vac 50Hz 5A resistive 1A inductive XP 8 1 8 2 Heat pump fault programmable output CAUTION not configured in the factory set H84 4...

Страница 44: ...appliance s rating plate Ensure that the voltage is definitive and within the tolerance limits 5 Before switching on check if all of the cover panels have been fitted and attached with the appropriate...

Страница 45: ...ting is required before the planned commissioning date back up generators may be used Ecomod heating system only via the tank back up resistors Ecomod hot water system via the gas boiler and the coil...

Страница 46: ...46 74 00U07352250 A_ EN AHP60 26 32 kW Installation Use and Maintenance Figure 15 Operating diagram 4 5 Operating diagram 4 5 1 26 32 kW...

Страница 47: ...nsor LR Fluid bottle TE SD 1 Temperature sensor on suction line F Filter TE DT 1 Compressor outlet temperature sensor SV Pressure socket PSH 1 HP pressure switch automatic reset HC 1 Housing resistor...

Страница 48: ...eau sortie t3 T aspir compres t4 T refoul compres t6 non utilis t7 non utilis t9 Pression basse t10 Pression haute t11 non utilis OH1 Heures compres OHP Heures pompe Only if fault in progress Only if...

Страница 49: ...LED ON LED if the compressor is active OFF if the compressor is switched off FLASHING if timer is counting down to start the compressor Not used in this application Frost free resistor LED ON LED if...

Страница 50: ...r Only if a USB stick is present see software instructions Firmware version Fir Installer Error history Hist Installer Only if there is data in the history Access the PSS menu to enter the maintenance...

Страница 51: ...s are lost and the password needs to be entered once again 5 4 Error menu Err This menu is only displayed if there are errors in progress It allows all of the ongoing errors to be viewed If this is a...

Страница 52: ...ror codes and diagnostic assistance When the heat pump is at fault it displays OFF and the alarm light is on To see the error code you must use PRG2 twice If an automatic reset fault appears the heat...

Страница 53: ...nto the well and that there is heat dissipating paste Check the refrigerant level E020 Inverter or pressure sensor alarm If the compressors has been operating for more than 150 seconds if the low pres...

Страница 54: ...1 sensor is securely attached to the terminals XC 8 1 XC 8 2 E641 Failure of the compressor discharge sensor intervention of the manual reset pressure switch closed 42 8bar open 34bar The DT1 sensor i...

Страница 55: ...the LP1 sensor is attached correctly to the terminals XC 17 1 XC 17 2 E701 High pressure sensor failure The HP1 high pressure sensor is defective Check that the HP1 sensor is attached correctly to th...

Страница 56: ...nd the fan board to determine if the opto coupler is working If the LEDs of the compressor inverter board INV1 are not flashing and the board is powered the board INV1 needs to be changed 6 3 Inverter...

Страница 57: ...supply voltage variations are too high Check supply voltage Temporary current cut occurred Supply terminals are screws are weak Check the terminals connections strength PFC converter failure Check pr...

Страница 58: ...lution E961 Abnormal condition reduce frequency for stop Driver output current or housing temperature exceeded the protection limits The rotor may be stopped since a long time Reduce compressor load R...

Страница 59: ...cases we recommend filling the system using an external tap that has been fitted by the installer 7 2 Filling the outdoor unit with water Refer to paragraph 3 6 3 7 3 Prolonged shutdown The methods f...

Страница 60: ...be where it is necessary to desolder the pipes we strongly recommend cutting the pipes and not desoldering them with a torch as the flame may trigger the combustion of any oil present It is forbidden...

Страница 61: ...rs on the hydraulic circuit X Clean the finned battery with compressed air X Check if the electrical terminals inside the electrical cabinet and on the compressor terminals are attached correctly X Ti...

Страница 62: ...leaning treatment every three months Wash preferably with hot water 40 60 C and a pH neutral detergent then rinse thoroughly with cold water 50 L m If the maintenance personnel notices that the protec...

Страница 63: ...y qualified technical personnel Place the appliance in a suitable place where there is no risk of leakage of flammable gas Make the installation area inaccessible to third parties Presence of dust wat...

Страница 64: ...ay increase weight Consult the table be fore the maintenance phase or refer to the component label in question and choose the most suitable equipment posture for the work to be performed taking into a...

Страница 65: ...Sources of ignition When working on a refrigeration circuit containing or having contained flammable refrigerant it is forbidden to use ignition sources that could cause the refrigerant to ignite Remo...

Страница 66: ...h substances that may cause corrosion Exception refrigerant lines must be made of corrosion resistant materials or be sufficiently protected against corrosion 7 Checking the electrical components The...

Страница 67: ...on components suitable for use in flammable atmospheres While we cannot completely rule out exceeding the permissible voltages and currents permanent capacitive or inductive loads must not be connecte...

Страница 68: ...circuit for repair or other reasons it should be done according to standard procedures In general special care must be taken with regard to the flammability of the refrigerant The following procedure...

Страница 69: ...rain equipment We recommend that first of all the refrigerant is recovered Before draining take samples of the oil and refrigerant if the refrigerant needs to be treated The important factor is that t...

Страница 70: ...tles must contain a safety valve and shut off valves that are firmly attached and in good condition Empty recycling bottles are evacuated and must be cooled down before the suction process if possible...

Страница 71: ...must not be put with domestic waste and must be collected separately When the appliance has reached the end of its life cycle and needs to be replaced a number of recommendations must be followed the...

Страница 72: ...ersons with appropriate technical training obtained through courses recognised by the competent authorities The same precautions described in the previous paragraphs must be followed Special attention...

Страница 73: ...01 07 2022 73 74 AHP60 26 32 kW Installation Use and Maintenance...

Страница 74: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...